Ultima Compact™
Chillers
51
Ultima Compact 30-150kW Technical Manual 9690553 V1.2.0_10_2019
Notes:
Units
UCCL050SR-2AJ0
UCCL050DR-2ADD
UCCL060SR-2AK0
SEPR
1,3,5
6.21
5.98
6.04
SEPR Tier
2 (2021)
2 (2021)
2 (2021)
Annual Electricity Consumption
kWh/a
57389.0
60599.0
65474.0
Rated Refrigerant Capacity P
A
1,3,5
kW
48.1
48.9
53.4
Rated Power Input D
A
kW
17.6
17.3
20.7
Rated EER
DC,A
2.74
2.82
2.58
Declared Refrigerant Capacity P
B
1,3,5
kW
53.3 / 27.8
54.2 / 25.9
59.3 / 31.2
Declared Power Input D
B
kW
13.6 / 6.6
13.4 / 7.3
15.9 / 7.5
Declared EER
DC,B
3.92 / 4.23
4.03 / 3.55
3.72 / 4.14
Declared Refrigerant Capacity P
C
1,3,5
kW
58.0 / 30.0
58.9 / 28.5
64.9 / 33.7
Declared Power Input D
C
kW
10.3 / 5.2
10.1 / 5.5
11.9 / 5.9
Declared EER
DC,C
5.64 / 5.78
5.82 / 5.14
5.44 / 5.69
Declared Refrigerant Capacity P
D
1,3,5
kW
62.5 / 32.3
63.4 / 31.1
70.2 / 36.3
Declared Power Input D
D
kW
7.3 / 3.9
7.2 / 4.0
8.6 / 4.5
Declared EER
DC,D
8.51 / 8.21
8.84 / 7.74
8.16 / 8.05
SSCEE
2,3,5
%
151.4%
129.2%
152.9%
SSCEE Tier
Tier 1 (2018) NOT Compliant Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5
kW
48.2
n/a
53.5
Declared Cooling Capacity 35°C Pdc 2,3,5
kW
48.1
n/a
53.4
Declared EER
d
35°C
2.74
n/a
2.58
Declared Cooling Capacity 30°C Pdc 2,3,5
kW
53.5 / 27.3
n/a
59.3 / 30.5
Declared EER
d
30°C
3.38 / 3.67
n/a
3.24 / 3.65
Declared Cooling Capacity 25°C Pdc 2,3,5
kW
30.1 / 0.0
n/a
33.7 / 0.0
Declared EER
d
25°C
4.53 / 0.00
n/a
4.62 / 0.00
Declared Cooling Capacity 20°C Pdc 2,3,5
kW
33.1 / 0.0
n/a
37.1 / 0.0
Declared EER
d
20°C
5.73 / 0.00
n/a
5.96 / 0.00
Sound Power Level
dB(A)
79
n/a
78
Air Volume
m³/h
23307
n/a
23307
Off mode P
OFF
kW
0.035
n/a
0.035
Thermostat-off mode P
TO
kW
0.353
n/a
0.389
Standby Mode P
SB
kW
0.050
n/a
0.050
Crankcase heater mode P
CK
kW
0.064
n/a
0.064
Capacity Control
Staged
Staged
Staged
Technical Data
Ecodesign
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21.
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2018.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2018.
(5) All performance data based upon standard waterside configuration.
(6) Please contact Airedale regarding Non Compliant selections.
Te
ch
nic
al