Ultima Compact™
Chillers
52 Ultima Compact 30-150kW Technical Manual 9690553 V1.2.0_10_2019
Notes:
Units
UCCL060DR-2AEE
UCCL070SR-2AL0
UCCL070DR-2AFF
SEPR
1,3,5
5.75
5.88
5.51
SEPR Tier
2 (2021)
2 (2021)
2 (2021)
Annual Electricity Consumption
kWh/a
69811.0
75965.0
82019.0
Rated Refrigerant Capacity P
A
1,3,5
kW
54.2
60.2
61.0
Rated Power Input D
A
kW
20.5
23.5
23.2
Rated EER
DC,A
2.65
2.56
2.63
Declared Refrigerant Capacity P
B
1,3,5
kW
60.3 / 28.9
67.0 / 35.4
67.9 / 32.7
Declared Power Input D
B
kW
15.7 / 8.5
18.5 / 8.7
18.1 / 9.8
Declared EER
DC,B
3.85 / 3.42
3.63 / 4.09
3.75 / 3.34
Declared Refrigerant Capacity P
C
1,3,5
kW
65.9 / 31.9
73.4 / 38.4
74.3 / 36.1
Declared Power Input D
C
kW
11.7 / 6.4
14.1 / 6.9
13.8 / 7.5
Declared EER
DC,C
5.63 / 4.99
5.20 / 5.55
5.38 / 4.78
Declared Refrigerant Capacity P
D
1,3,5
kW
71.3 / 34.9
79.8 / 41.5
80.7 / 39.6
Declared Power Input D
D
kW
8.4 / 4.7
10.3 / 5.3
10.0 / 5.6
Declared EER
DC,D
8.48 / 7.47
7.75 / 7.88
8.08 / 7.10
SSCEE
2,3,5
%
128.7%
150.9%
125.6%
SSCEE Tier
NOT Compliant Tier 1 (2018) NOT Compliant
Rated Cooling Capacity P
rated,c
2,4,5
kW
n/a
60.4
n/a
Declared Cooling Capacity 35°C Pdc 2,3,5
kW
n/a
60.2
n/a
Declared EER
d
35°C
n/a
2.56
n/a
Declared Cooling Capacity 30°C Pdc 2,3,5
kW
n/a
66.9 / 34.8
n/a
Declared EER
d
30°C
n/a
3.17 / 3.63
n/a
Declared Cooling Capacity 25°C Pdc 2,3,5
kW
n/a
38.3 / 0.0
n/a
Declared EER
d
25°C
n/a
4.54 / 0.00
n/a
Declared Cooling Capacity 20°C Pdc 2,3,5
kW
n/a
42.3 / 0.0
n/a
Declared EER
d
20°C
n/a
5.81 / 0.00
n/a
Sound Power Level
dB(A)
n/a
79
n/a
Air Volume
m³/h
n/a
23307
n/a
Off mode P
OFF
kW
n/a
0.035
n/a
Thermostat-off mode P
TO
kW
n/a
0.424
n/a
Standby Mode P
SB
kW
n/a
0.050
n/a
Crankcase heater mode P
CK
kW
n/a
0.064
n/a
Capacity Control
Staged
Staged
Staged
Technical Data
Ecodesign
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21.
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2018.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2018.
(5) All performance data based upon standard waterside configuration.
(6) Please contact Airedale regarding Non Compliant selections.
Te
ch
ni
ca
l