TurboChill™
Chillers
17
TurboChill Water Cooled Technical Manual 9216326 V1.10.0 06_2017
Flow Proving Device*
Evaporator and condenser differential pressure sensors facilitate low flow limiting and pressure drop monitoring via the
microprocessor which shall be fitted to ensure correct unit water flow.
Pump Interlock*
Provision for a pump interlock is available within the control panel.
Water Flow Switch*
If selected, a water flow switch shall be fitted ensuring integrity of the cooling solution flow. The flow switch shall protect
the chiller against low water flow conditions.
*Each feature is a flow proving device and 2 out of the 3 should be fitted to any unit to validate
warranty.
CAUTION
Water Connections
Water inlet and outlet connections are of a grooved and clamped type construction, enabling easy pipework termination.
The unit is supplied with a counter pipe and coupling assembly for quick installation. Water inlet and outlet are located at
the end of the unit.
Introduction