TurboChill Water Cooled Technical Manual 9216326 V1.10.0 06_2017
Example:
TCW
1
1
R
C1
E1
-
S
-
0
TurboChill Watercooled
Number of Circuits
Number of Compressors
Noise Variant (Regular
R
or Extra
X
Quiet)
Condenser Code (C1)
Evaporator Code (E1)
Compressor Code (S,G,L)
400V 3PH 50Hz Power Supply
Specifier’s Guide
Nomenclature
Introduction
The Airedale TurboChill Water Cooled chiller uses the technologically superior centrifugal TurboCor compressors.
Designed for a cooling capacity of 150kW to 1488kW*, the nominal operating conditions are based on EN14511 rating
conditions for water cooled chillers which are 12/7°C Evaporator and 30/35°C Condenser water temperatures.
Refrigerant
The range has been designed and optimised for operation with ozone benign R134a refrigerant or R1234ze(E)
refrigerant.
Construction
The base shall be fabricated from galvanised steel to ensure a rigid, durable, weatherproof construction.
Unit panels shall be manufactured from galvanised sheet steel coated with epoxy baked powder paint to provide a
durable and weatherproof finish.
Standard unit colour shall be Light Grey (RAL 7035).
The Compressor, Evaporator and Condenser shall be mounted on a rigid galvanised heavy-duty sub frame.
Electrical panels shall be situated at one side of the unit.**
*Capacity data based on minimum capacity of one module to maximum capacity of four modules.
**Only low noise (X) models will be supplied with enclosed panels.