TurboChill Water Cooled Technical Manual 9216326 V1.13.0 07_2018
Pad Type
Components/Installation
1. M16 Bolt (Not Supplied)
2. Washer (Not Supplied)
3. Fixing Pad 6173231
4. Anti Vibration Pad 6173223
5. 2 x M16 Nut (Not Supplied)
6. Unit Base
7. Unit Mounting Plinth
1
2
3
2
5
4
3
6
7
Anti Vibration Mounting Pad Type
Clearance
Should the chiller be installed standalone/unable to move the unit, provison must be made for maintenance around the
chiller. The following minimum clearance is required:
A
B
B
C
Pipework
A - Clearance between units - 800mm
B - Clearance between unit and external walls - 800mm
C - Clearance for chiller - 2000mm
D - Clearance for chiller maneuverability - 3000mm
E - 50mm
Provision of 500mm is recommended above the unit for maintenance purposes.
E
E
D
Pipework
Start
position
Finish
Position
B
If the unit is mounted on a plinth, suitable fixings must be used.
IMPORTANT
Units unable to move