CR12 - CR165 50/60Hz
CONDENSERS
CR12
CR16
CR22
CR30
Unit Data
(1)
Nominal Run Amps
A
1.1
1.1
2.9
2.9
Maximum Start Amps
A
2.8
2.8
5.6
5.6
Recommended Mains Fuse
A
6
6
6
6
Max Mains Cable Incoming
mm²
6
6
6
6
Mains Supply
230V / 1Ph + N / 60Hz
Fan - Per Fan
Quantity
1
1
1
1
Motor Size
kW
0.24
0.24
0.63
0.63
Full Load Amps
A
1.1
1.1
2.9
2.9
Locked Rotor Amps
A
2.8
2.8
5.6
5.6
OPTIONAL EXTRAS
Short Case Axial Fan - Per Fan
Quantity
1
1
1
1
Motor Size
kW
0.61
0.61
1.4
1.4
Full Load Amps
A
2.8
2.8
6
6
Locked Rotor Amps
A
7
7
18
18
EC Condenser Fan - Per Fan
Quantity
1
1
1
1
Motor Size
kW
0.7
0.7
0.77
0.77
Full Load Amps
A
3.1
3.1
3.3
3.3
Technical Data
Electrical Data - 1
CR50
CR65
CR80
CR105
Unit Data
-1
Nominal Run Amps
A
5.8
5.8
8.7
8.7
Maximum Start Amps
A
11.2
11.2
16.8
16.8
Recommended Mains Fuse
A
10
10
16
16
Max Mains Cable Incoming
mm²
6
6
6
6
Mains Supply
230V / 1Ph + N / 60Hz
Fan - Per Fan
Quantity
2
2
3
3
Motor Size
kW
0.63
0.63
0.63
0.63
Full Load Amps
A
2.9
2.9
2.9
2.9
Locked Rotor Amps
A
5.6
5.6
5.6
5.6
OPTIONAL EXTRAS
Short Case Axial Fan - Per Fan
Quantity
2
2
3
3
Motor Size
kW
1.4
1.4
1.4
1.4
Full Load Amps
A
6
6
6
6
Locked Rotor Amps
A
18
18
18
18
EC Condenser Fan - Per Fan
Quantity
2
2
3
3
Motor Size
kW
0.77
0.77
0.77
0.77
Full Load Amps
A
3.3
3.3
3.3
3.3
(1)
Nominal data based on 35°C ambient and a 50°C mean condensing temperature and using standard fan.
31
Condenser Technical Manual 6666879 V1.2.0_05_2013
Te
ch
nic
al