![AIREDALE CR105 Technical Manual Download Page 25](http://html.mh-extra.com/html/airedale/cr105/cr105_technical-manual_2876538025.webp)
CR12 - CR165 50/60Hz
CONDENSERS
Mean Condensing
Ambient
Temperature °C
25°C
30°C
35°C
40°C
45°C
48°C
Output kW
Output kW
Output kW
Output kW
Output kW
Output kW
CR65
35
44.9
18.6
-
-
-
-
40
69.1
45.2
19.3
-
-
-
45
93.8
69.7
45.6
20
-
-
50
119.2
94.8
70.6
46.4
21
-
55
145.5
120.9
96.4
72
47.5
22.6
CR80
35
55.3
23
-
-
-
-
40
85.8
55.8
23.8
-
-
-
45
116.7
86.6
56.5
24.7
-
-
50
148.4
118.1
87.8
57.5
25.8
-
55
180.9
150.4
120
89.5
58.9
28.3
CR105
35
72.1
30
-
-
-
-
40
110.8
72.6
31
-
-
-
45
150.4
111.7
73.3
32.2
-
-
50
191.1
152.1
113.2
74.5
33.8
-
55
233.3
193.8
154.6
115.5
76.3
36.4
CR130
35
95.3
40.5
-
-
-
-
40
146.3
95.9
41.7
-
-
-
45
198.3
147.6
97
43.2
-
-
50
251.6
200.6
149.7
98.6
45.1
-
55
306.6
255.2
203.9
152.6
101
50.6
CR140
35
95.8
40.2
-
-
-
-
40
147.2
96.3
41.5
-
-
-
45
199.6
148.3
97.2
43
-
-
50
253.5
201.6
150.1
98.7
44.9
-
55
309
256.8
204.8
152.9
101
48.3
CR165
35
124.8
53.5
-
-
-
-
40
191.6
125.6
55
-
-
-
45
259.6
193.2
126.9
56.9
-
-
50
329
262.3
195.7
128.9
59.2
-
55
400.6
333.4
266.4
199.3
131.8
66.6
Technical Data
Performance Data
(1)
Output kW refers to the condenser heat rejection.
Standard Variable Speed Head Pressure Control
Minimum Ambient Air DB °C
-20°C
Maximum Ambient Air DB °C
+48
Optional On/Off Head Pressure Control
Minimum Ambient Air DB °C
-0°C
Maximum Ambient Air DB °C
+48
Operating Limit
(1)
For conditions outside those quoted, please contact Airedale.
(2)
Low ambient kits are available for applications with temperatures below those quoted, please contact Airedale.
25
Condenser Technical Manual 6666879 V1.2.0_05_2013
Te
ch
nic
al