Ceiling Cassette 

 

The SLIMLINE PERFORMER Ceiling Cassette – Ductless Mini-Split

 

3

Technical Manual : AIR 8-105.5 

 

 

General Description 

 

MODEL 
IDENTIFICATION 

CEILING CASSETTE UNITS 

 

CSD, CSH 
or CCW 

Base Model:

CSD = Ceiling Cassette Unit – DX Cooling 
CSH = Ceiling Cassette Unit – Heat Pump 
CCW = Ceiling Cassette Unit – Chilled Water 

 

2/ or _ (blank) 

Cabinet Size:

2/ = Small Body (2 X 2 Series) 
_  = Medium Body (3 X 3 Series) or Large Body (3 X 4 Series) 

 

8 to 42 

Model Size:

Nominal Cooling in Mbh (See Performance Data for Details) 

 

EM, MC or CA 

Control Type:

EM = Electro-Mechanical Control 
MC = Microprocessor Controlled – Remote Control via Infrared or Pendant 
CA = Carel Controller 

 

Example: 

CSD 18EM

 =  

Ceiling Cassette Unit, DX Cooling, 18,000 Nominal BTU/Hr,  
Electro-Mechanical Control 

 

STANDARD FEATURES 

Construction 

Cases are manufactured from lightweight galvanized sheet steel with integral fan mounting 
rails for added strength. Fire resistant foam insulation (to UL94 VO) is fitted internally to 
provide both thermal and acoustic insulation. 

 

 

Evaporator 

All direct expansion units include a factory installed thermal expansion valve and utilize large 
surface area evaporator coils ideally positioned to optimize heat transfer and airflow. Each 
evaporator is manufactured from refrigeration quality copper tubes with mechanically bonded 
aluminum fins. 

 

 

Chilled Water Coil 

All chilled water units utilize large surface area coils positioned to optimize heat transfer and 
airflow. Each coil is manufactured from refrigeration quality copper tubes with mechanically 
bonded aluminum fins and are circuited from headers to ensure low water pressure drops. 

 

 

Fan 

All units, utilizing backward curved centrifugal fans, are staticly and dynamically balanced for 
quiet operation. Fan impellers are made from either aluminum or fire retardant plastic (UL94 
VO) for light weight and corrosion resistant operation. Fans are driven by an enclosed multi-
speed external rotor motor allowing good heat dissipation and an increased motor efficiency. 
Fans come complete with thermal overload protection and sealed-for-life lubricated bearings.

 

 

Filtration 

Wire framed filters are fitted. These are re-usable and may be vacuum cleaned. 

 

 

Condensate Pump 

A condensate pump and check valve are fitted to carry water out of the unit and stop water 
from flowing back into the condensate tray. The pump is fixed to a mounting bracket which 
can be withdrawn from the side of the chassis and incorporates an inspection hole to allow a 
visual check of the pump during operation. A float switch is fitted to stop the cooling action 
should the pump become blocked or fail. 

 

 

Air Vanes 

Air outlet vanes are designed to prevent condensation from forming. Vanes are manually 
adjustable on the 2 x 2 model units but driven by an electric motor on all other model units. 
Where fitted, the motorized air vanes can be set to auto sweep or can be stopped in a fixed 
position. Polystyrene blanking pieces are supplied with Cassette packing so that up to two 
fascia discharge slots can be blanked off. 

 

 

Alarm Status Relay 

The unit shall include a relay for unit failure notification.  Normally open contact available for 
field connection. 

 

 

Start / Stop Terminals 

The unit shall include terminals for remote start/stop of the unit.  The unit is enabled when 
contact between the terminals is closed.  (only on Electro-Mechanical controls) 

 

Summary of Contents for CCW 18

Page 1: ...AIR 8 105 5 September 2012 The SLIMLINE PERFORMER Ceiling Cassette Ductless Mini Split Models CSD CSH and CCW T E C H N I C A L M A N U A L 3087217 ...

Page 2: ... individual comfort Airedale Cassettes are available with electro mechanical or micro processor based controls The micro processor controller includes an infrared transmitter which enables room conditions to be maintained at a user defined set point Airedale Cassettes are also available with Carel microprocessor controls and network cards to allow units to be connected to a Building Management Sys...

Page 3: ...headers to ensure low water pressure drops Fan All units utilizing backward curved centrifugal fans are staticly and dynamically balanced for quiet operation Fan impellers are made from either aluminum or fire retardant plastic UL94 VO for light weight and corrosion resistant operation Fans are driven by an enclosed multi speed external rotor motor allowing good heat dissipation and an increased m...

Page 4: ...iver displays ON OFF cool or heat and timer alarm status Controls Option 3 Carel Controller The unit shall be fitted with a programmable microprocessor controller designed to operate the unit according to pre engineered control strategies The Carel controller requires a wall sensor wall stat or network interface card LonWorks Card for Carel Controller The Carel microprocessor controller shall come...

Page 5: ...o cover the unit housing when the unit is not mounted in a drop ceiling Painted Sky White with hammertone finish Two Position Spring Return Control Valves For control of chilled water or hot water flow a three way three port diverting type valve or a two way two port control valve is supplied loose for on site installation Actuation is via a 24V signal from the unit s electrical panel On a four pi...

Page 6: ... 32200 26200 CSD CSH 36 75 35000 29200 34600 28200 34000 26800 80 38200 30400 37800 29400 37000 27800 72 37800 31600 37200 30200 36800 29400 CSD CSH 42 75 39500 32400 39000 31000 38500 30000 80 42500 33400 42000 32000 41500 31000 Table 6 2 Heating Performance Heat Pump Units Entering Air DB ºF Fan Speed High Medium Low Model TC BTU h TC BTU h TC BTU h 50 19100 18900 18600 CSH 18 60 17800 17600 172...

Page 7: ...ow Pr Drop TC SC Flow Pr Drop Model BTU h BTU h gpm PSI BTU h BTU h gpm PSI 72 5 236 5 156 1 1 2 4 3 999 3 999 0 8 1 5 CCW2 8 75 6 528 5 989 1 3 3 5 4 729 4 729 1 0 2 0 80 10 037 7 529 2 0 7 6 7 026 6 107 1 4 4 0 72 8 723 7 261 1 8 1 9 5 623 5 623 1 1 0 9 CCW2 12 75 10 831 8 173 2 2 2 7 7 502 6 604 1 5 1 4 80 14 435 9 644 2 9 4 6 11 236 8 200 2 3 2 9 72 13 728 12 126 2 8 1 9 9 295 9 295 1 9 0 9 CC...

Page 8: ...CCW 33 60 51 120 5 3 3 5 70 46 555 4 9 3 0 50 62 005 6 5 4 8 CCW 36 60 56 762 5 9 4 1 70 51 600 5 4 3 5 Table 8 2 Heating Performance DX Cooling Only and Heat Pump Units with Optional Hot Water Coil Hot Water 180ºF Inlet 160ºF Outlet Entering Air Heating Capacity Flowrate Pressure Drop Model DB ºF 50 RH BTU h GPM PSI 50 46 389 4 8 1 3 CSD CSH 18 60 42 598 4 4 1 1 70 38 746 4 0 0 9 50 50 279 5 3 1 ...

Page 9: ...H BTU h GPM PSI 50 28 389 3 0 11 0 CCW2 8 60 25 903 2 7 9 4 70 23 605 2 5 8 0 50 33 471 3 5 4 6 CCW2 12 60 30 715 3 2 4 0 70 27 995 2 9 3 4 50 60 388 6 3 5 7 CCW 18 60 55 127 5 8 4 8 70 49 706 5 2 4 0 50 65 350 6 8 6 5 CCW 20 60 59 887 6 3 5 6 70 54 118 5 7 4 7 50 99 476 10 4 10 1 CCW 33 60 91 494 9 6 8 8 70 82 986 8 7 7 4 50 114 225 11 9 13 0 CCW 36 60 105 132 11 0 11 2 70 95 896 10 0 9 5 Notes 1...

Page 10: ... 2 3 4 10 11 16 19 9 16 19 1 2 12 9 16 1 7 16 22 15 16 7 8 22 1 2 8 13 16 11 5 16 4 11 16 3 11 16 2 5 8 O 5 3 16 6 1 2 5 1 8 3 3 4 2 1 16 2 5 8 A A VIEW A A 9 13 16 1 1 8 2 3 4 5 7 8 9 5 10 6 1 CW Inlet 2 CW Outlet 3 HW Coil Inlet Optional 4 HW Coil Outlet Optional 5 Branch Duct Opening x3 6 Fresh Air Intake x2 7 Pump Inspection Port 8 Condensate Drain 9 Control Panel 10 Mounting Bracket 1 2 3 4 3...

Page 11: ...6 31 3 8 28 9 16 12 9 16 1 13 16 4 5 8 6 8 5 8 1 5 8 5 5 16 7 3 4 2 3 4 2 3 4 4 7 8 4 15 16 32 5 16 5 3 8 3 3 16 1 5 16 3 8 13 16 8 11 16 11 13 16 3 1 8 7 13 16 2 3 4 VIEW A A A A 2 5 1 4 10 5 6 7 8 9 3 5 3 8 1 CW Coil Inlet 2 CW Coil Outlet 3 HW Coil Inlet Optional 4 HW Coil Outlet Optional 5 Fresh Air Intake x3 6 Branch Duct Opening x4 7 Pump Inspection Port 8 Condensate Drain 9 Control Panel 10...

Page 12: ...1 1 2 2 5 8 28 11 16 12 9 16 28 9 16 1 7 8 43 1 2 7 8 8 13 16 19 5 8 12 7 16 6 3 8 3 5 8 3 3 8 3 6 4 5 8 7 3 16 2 3 16 4 3 4 7 9 16 9 13 16 1 5 8 4 7 8 2 3 4 2 3 4 3 1 8 9 13 16 2 3 4 5 10 2 5 4 3 1 6 7 9 8 1 CW Coil Inlet 2 CW Coil Outlet 3 HW Coil Inlet Optional 4 HW Coil Outlet Optional 5 Fresh Air Intake x3 6 Branch Duct Opening x4 7 Pump Inspection Port 8 Condensate Drain 9 Control Panel 10 M...

Page 13: ...3 4 1 5 8 2 3 4 4 7 8 3 7 16 A A VIEW A A 6 7 8 9 5 5 1 2 4 3 10 1 DX Suction Line 2 DX Liquid Line 3 HW Coil Inlet Optional 4 HW Coil Outlet Optional 5 Fresh AIr Intake x3 6 Branch Duct Opening x4 7 Pump Inspection Port 8 Condensate Drain 9 Control Panel 10 Mounting Bracket 31 3 8 1 7 8 28 9 16 12 9 16 28 11 16 32 3 8 4 3 4 11 5 8 2 5 8 37 37 11 16 Figure 13 1 Dimensions Medium Chassis Model CSD ...

Page 14: ...15 15 3 1 8 2 3 4 9 13 16 VIEW A A A A 8 13 16 2 7 8 2 7 8 4 7 8 6 5 16 4 7 16 2 7 8 3 1 2 4 7 8 6 7 16 1 2 3 4 9 7 8 6 10 5 5 43 1 2 44 7 16 1 DX Suction Line 2 DX Liquid Line 3 HW Coil Inlet Optional 4 HW Coil Outlet Optional 5 Fresh AIr Intake x3 6 Branch Duct Opening x4 7 Pump Inspection Port 8 Condensate Drain 9 Control Panel 10 Mounting Bracket Figure 14 1 Dimensions Large Chassis Model CSD ...

Page 15: ...n in 3 4 3 4 3 4 3 4 3 4 Liquid in 3 8 3 8 3 8 3 8 3 8 Condensate ID in 3 8 3 8 3 8 3 8 3 8 Filtration Type Wire Framed Periframe Quantity 2 2 3 3 3 Arrestance 80 80 80 80 80 Condensate Pump Maximum Head in 30 30 30 30 30 Nominal Flowrate gpm 0 1 0 1 0 1 0 1 0 1 Options Electric Heating Capacity kW 3 0 3 0 5 0 5 0 5 0 HW Heating Capacity 5 BTU h 38 746 41 993 56 609 59 600 64 268 HW Coil Connectio...

Page 16: ...8 7 8 7 8 7 8 7 8 Chilled Water Outlet in 5 8 5 8 7 8 7 8 7 8 7 8 Condensate ID in 3 8 3 8 3 8 3 8 3 8 3 8 Filtration Type Wire Framed Periframe Quantity 1 1 2 2 3 3 Arrestance 80 80 80 80 80 80 Condensate Pump Maximum Head in 30 30 30 30 30 30 Nominal Flowrate gpm 0 1 0 1 0 1 0 1 0 1 0 1 Options Electric Heating Capacity kW 1 5 1 5 3 0 3 0 5 0 5 0 HW Heating Capacity 2 BTU h 13 799 N A 29 258 30 ...

Page 17: ...Color Champagne Dimensions Weights Height includes Fan Guard in 28 28 28 28 30 Width in 23 23 23 29 29 Depth in 23 23 23 29 29 Weight lb 97 129 131 145 173 Compressor Type Rotary Recip Recip Recip Recip Crankcase Heater Fitted No No No No No Condenser Coil Construction Plate Fin Microchannel Plate Fin Microchannel Plate Fin Microchannel Plate Fin Microchannel Plate Fin Microchannel Connections 1 S...

Page 18: ... Champagne Dimensions Weights Height includes Fan Guard in 28 32 36 40 40 Width in 34 34 34 34 34 Depth in 34 34 34 34 34 Weight lb 172 184 196 208 208 Compressor Type Scroll Recip Recip Recip Scroll Crankcase Heater Fitted No Yes Yes Yes No Condenser Coil Construction Round Tube Plate Fin Round Tube Plate Fin Round Tube Plate Fin Round Tube Plate Fin Round Tube Plate Fin Connections 1 Suction in ...

Page 19: ...MCA A 1 5 2 0 2 8 Recommended Fuse A 10 10 10 1 Standard Unit fitted with optional electric heating elements Available with 230V model units only 2 Standard unit fitted with optional booster transformer for connection to a 115V electrical supply Electric heat not available in conjunction with this option Table 19 2 Electrical Data Condensers for DX Cooling Only Units Cassette Unit CSD 18 CSD 24 CS...

Page 20: ... Minimum recommended overcurrent protection Table 20 2 Sound Data Ceiling Cassette Units MERCER TABLE Models Fan Speed SPL dBA 1 Sound Pressure Frequency Spectrum dB 1 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz High 29 37 37 33 29 21 14 10 CCW2 8 Med 26 34 34 30 24 15 12 10 Low 22 31 29 25 17 8 10 8 High 35 42 41 38 35 28 21 12 CCW2 12 Med 32 38 39 36 32 24 16 10 Low 29 37 37 33 29 21 14...

Page 21: ... 21 1 Sound Data Condensers for DX Cooling Only and Heat Pump Units Model Units Cooling Heating YCJD18 dBA 75 YCJD24 dBA 76 YCJD30 dBA 76 YCJD36 dBA 76 YCJD42 dBA 76 YHJD18 dBA 70 1 70 9 YHJD24 dBA 75 8 75 0 YHJD30 dBA 74 7 74 8 YHJD36 dBA 76 5 76 5 YHJD42 dBA 72 0 76 0 Rated in accordance with ARI 270 95 standards ...

Page 22: ...nly The unit contains enough refrigerant for matching indoor coils and 15 feet of interconnecting piping The small base dimension means less space is required on the ground or roof Top Discharge The warm air from the top mounted fan is blown up and away from the structure and any landscaping This allows compact location on multi unit applications Low Operating Sound Level The upward air flow carri...

Page 23: ...wiring connections Available in sweat connect models only The unit contains enough refrigerant for matching indoor coils and 15 feet of interconnecting piping The small base dimension means less space is required on the ground or roof Top Discharge The warm air from the top mounted fan is blown up and away from the structure and any landscaping This allows compact location on multi unit applicatio...

Page 24: ...it Technical Manual AIR 8 105 5 Ceiling Cassette Commercial Products Group Modine Manufacturing Company 1500 DeKoven Avenue Racine WI 53403 2552 Phone 1 866 823 1631 toll free Fax 1 800 204 6011 www airedaleusa com Modine Manufacturing Company 2012 Litho in USA ...

Reviews: