![AIREDALE CCW 18 Technical Manual Download Page 16](http://html.mh-extra.com/html/airedale/ccw-18/ccw-18_technical-manual_2876537016.webp)
16
The SLIMLINE PERFORMER Ceiling Cassette – Ductless Mini-Split
Technical Manual : AIR 8-105.5
Ceiling Cassette
Table 16.1 – Technical Data – Chilled Water Units
Units
CCW2/8
CCW2/12 CCW
18 CCW
20 CCW
33 CCW
36
Nominal Cooling Capacity (1)
BTU/h
6,601 11,091 17,592 19,087 29,722 35,258
Construction
Material: Fascia
High Impact Polystyrene
Material: Chassis
Galvanized Steel
Color: Fascia
Pearl Grey
Fire rating
UL94 VO
Chilled Water Coil
Type
Finned Tube
Quantity
1
1
1
1
1
1
Face Area
Ft²
1.8
1.8
2.8
2.8
5.2
5.2
Nominal
Airflow
High
cfm
350 350 630 700 970 1160
Med
cfm
300 300 530 630 890 970
Low
cfm
260 260 500 530 785 890
Discharge
4-way
4-way
4-way
4-way
4-way
4-way
Unit water Volume
gal
0.29
0.29
0.45
0.45
0.79
0.79
Fan
Type
Centrifugal
Quantity
1
1
1
1
2
2
Diameter
in
12 12 15 15 14 14
Horsepower (per fan)
HP
1/8
1/8
1/8
1/8
1/8
1/8
Weights
Weight - Chassis
lb
40
40
64
64
97
97
Weight - Fascia
lb
5
5
18
18
21
21
Connections
Chilled Water Inlet
in
5/8
5/8
7/8
7/8
7/8
7/8
Chilled Water Outlet
in
5/8
5/8
7/8
7/8
7/8
7/8
Condensate (ID)
in
3/8
3/8
3/8
3/8
3/8
3/8
Filtration
Type
Wire Framed Periframe
Quantity
1
1
2
2
3
3
Arrestance
80%
80%
80%
80%
80%
80%
Condensate Pump
Maximum Head
in
30
30
30
30
30
30
Nominal Flowrate
gpm
0.1
0.1
0.1
0.1
0.1
0.1
Options
Electric Heating Capacity
kW
1.5
1.5
3.0
3.0
5.0
5.0
HW Heating Capacity (2)
BTU/h
13,799
N/A
29,258
30,946
46,455
51,600
HW Coil Connection (OD)
in
5/8
N/A
5/8
5/8
5/8
5/8
Max Branch Duct Connections
(qty)
2
2
2
2
2
2
Branch Duct Diameter
in
5
5
5
5
6
6
Ducted
Air
Volume
(3)
cfm
80 80 100 125 200 220
Fresh Air Connections
(qty)
1-2
1-2
1-3
1-3
1-3
1-3
Fresh Air Duct Diameter
in
3
3
3
3
3
3
Fresh Air Volume (4)
cfm
40
40
60
65
90
95
(1) Nominal cooling capacity based on 80/67°F DB/WB and water temperature of 45ºF inlet / 55ºF outlet.
(2) Nominal heating capacity based on 70/60°F DB/WB and water temperature of 180ºF inlet / 160ºF outlet.
(3) Maximum air volume available through one branch duct 6' long, with Cassette fan(s) at high speed and corresponding fascia
aperture closed.
(4) Maximum fresh air through all knockouts connected to one 10' long duct with fan at high speed.