AIREDALE CCW 18 Technical Manual Download Page 15

Ceiling Cassette 

 

The SLIMLINE PERFORMER Ceiling Cassette – Ductless Mini-Split

 

15

Technical Manual : AIR 8-105.5 

 

 

 

Table 15.1 – Technical Data – DX Cooling Only and Heat Pump Units 

 

Units 

CSD/CSH 18 

CSD/CSH 24 

CSD/CSH 30 

CSD/CSH 36 

CSD/CSH 42

 

Nominal Cooling Capacity (1) 

BTU/h 

19200 

23000 

31400 

38200 

42500 

Nominal Heating Capacity (2) 

BTU/h 

16400 

21400 

27400 

32400 

37200 

Nominal 

System 

SEER 

(3) 

 

13 13 13 13 13 

HSPF 

 

7.7 7.7 7.7 7.7 7.7 

Construction 

  

 

 

 

 

 

Material: Fascia 

  

High Impact Polystyrene 

Material: Chassis 

  

Galvanized Steel 

Color: Fascia 

  

Pearl Grey 

Fire rating 

  

UL94 VO 

Evaporator 

  

 

 

 

 

 

Type  

 

Finned Tube

Quantity 

 

 

1 1 1 1 1 

Face 

Area 

Ft² 

4.0 4.0 5.2 5.2 5.2 

Nominal Airflow                 High 

cfm 

590 

670 

920 

1000 

1130 

Med 

cfm 

540 590 800 920 1000 

 

Low 

cfm 

465 540 680 800 920 

Discharge 

 

 4-way 4-way 4-way 4-way 4-way 

Fan 

  

 

 

Type  

 

Centrifugal

Quantity 

 

 

1 1 2 2 2 

Diameter 

in 

14 14 14 14 14 

Horsepower 

(per 

fan)  HP 

1/8 1/8 1/8 1/8 1/8 

Refrigeration 

  

  

  

  

  

  

Number of Circuits 

  

Refrigerant 

Type 

 

 R-410A R-410A R-410A R-410A R-410A 

Weights 

  

  

  

  

  

  

Weight 

Chassis 

lb 

66 66 97 97 97 

Weight 

Fascia 

lb 

18 18 21 21 21 

Connections (4) 

  

  

  

  

  

  

Suction 

in 

3/4 3/4 3/4 3/4 3/4 

Liquid 

in 

3/8 3/8 3/8 3/8 3/8 

Condensate 

(ID) 

in 

3/8 3/8 3/8 3/8 3/8 

Filtration 

  

 

 

Type  

 

Wire Framed Periframe

Quantity 

 

 

2 2 3 3 3 

Arrestance 

 

 

80% 80% 80% 80% 80% 

Condensate Pump 

  

  

  

  

  

  

Maximum 

Head 

in 

30 30 30 30 30 

Nominal 

Flowrate 

gpm 

0.1 0.1 0.1 0.1 0.1 

Options 

  

  

  

  

  

  

Electric 

Heating 

Capacity 

kW 

3.0 3.0 5.0 5.0 5.0 

HW Heating Capacity (5) 

 BTU/h 

38,746 

41,993 

56,609 

59,600 

64,268 

HW Coil Connection (OD) 

in 

7/8 

7/8 

7/8

7/8

 

7/8 

Max 

Branch 

Duct 

Connections 

(qty) 

2 2 2 2 2 

Branch 

Duct 

Diameter 

in 

5 5 6 6 6 

Branch Duct Air Volume (6) 

cfm 

115 

130 

180 

200 

220 

Fresh Air Connections 

(qty) 

1-3 

1-3 

1-3 

1-3 

1-3 

Fresh 

Air 

Duct 

Diameter 

in 

3 3 3 3 3 

Fresh 

Air 

Volume 

(7) cfm 

60 65 85 90 95 

(1)  Nominal cooling capacity based on 80/67°F DB/WB and 95/75ºF DB/WB ambient 
(2)  Nominal heating capacity based on 70/60°F DB/WB and 47/43°F DB/WB ambient. 
(3)  Test conditions based on ARI 210/240. 
(4)  Refrigerant line sizes should always match condensing unit connection sizes. 
(5)  Nominal heating capacity based on 70/60°F DB/WB and water temperature of 180ºF inlet / 160ºF outlet. 
(6)  Maximum air volume available through one branch duct 6' long, with Cassette fan(s) at high speed and corresponding fascia 
aperture closed. 
(7)  Maximum fresh air through all knockouts connected to one 10' long duct with fan at high speed. 

Summary of Contents for CCW 18

Page 1: ...AIR 8 105 5 September 2012 The SLIMLINE PERFORMER Ceiling Cassette Ductless Mini Split Models CSD CSH and CCW T E C H N I C A L M A N U A L 3087217 ...

Page 2: ... individual comfort Airedale Cassettes are available with electro mechanical or micro processor based controls The micro processor controller includes an infrared transmitter which enables room conditions to be maintained at a user defined set point Airedale Cassettes are also available with Carel microprocessor controls and network cards to allow units to be connected to a Building Management Sys...

Page 3: ...headers to ensure low water pressure drops Fan All units utilizing backward curved centrifugal fans are staticly and dynamically balanced for quiet operation Fan impellers are made from either aluminum or fire retardant plastic UL94 VO for light weight and corrosion resistant operation Fans are driven by an enclosed multi speed external rotor motor allowing good heat dissipation and an increased m...

Page 4: ...iver displays ON OFF cool or heat and timer alarm status Controls Option 3 Carel Controller The unit shall be fitted with a programmable microprocessor controller designed to operate the unit according to pre engineered control strategies The Carel controller requires a wall sensor wall stat or network interface card LonWorks Card for Carel Controller The Carel microprocessor controller shall come...

Page 5: ...o cover the unit housing when the unit is not mounted in a drop ceiling Painted Sky White with hammertone finish Two Position Spring Return Control Valves For control of chilled water or hot water flow a three way three port diverting type valve or a two way two port control valve is supplied loose for on site installation Actuation is via a 24V signal from the unit s electrical panel On a four pi...

Page 6: ... 32200 26200 CSD CSH 36 75 35000 29200 34600 28200 34000 26800 80 38200 30400 37800 29400 37000 27800 72 37800 31600 37200 30200 36800 29400 CSD CSH 42 75 39500 32400 39000 31000 38500 30000 80 42500 33400 42000 32000 41500 31000 Table 6 2 Heating Performance Heat Pump Units Entering Air DB ºF Fan Speed High Medium Low Model TC BTU h TC BTU h TC BTU h 50 19100 18900 18600 CSH 18 60 17800 17600 172...

Page 7: ...ow Pr Drop TC SC Flow Pr Drop Model BTU h BTU h gpm PSI BTU h BTU h gpm PSI 72 5 236 5 156 1 1 2 4 3 999 3 999 0 8 1 5 CCW2 8 75 6 528 5 989 1 3 3 5 4 729 4 729 1 0 2 0 80 10 037 7 529 2 0 7 6 7 026 6 107 1 4 4 0 72 8 723 7 261 1 8 1 9 5 623 5 623 1 1 0 9 CCW2 12 75 10 831 8 173 2 2 2 7 7 502 6 604 1 5 1 4 80 14 435 9 644 2 9 4 6 11 236 8 200 2 3 2 9 72 13 728 12 126 2 8 1 9 9 295 9 295 1 9 0 9 CC...

Page 8: ...CCW 33 60 51 120 5 3 3 5 70 46 555 4 9 3 0 50 62 005 6 5 4 8 CCW 36 60 56 762 5 9 4 1 70 51 600 5 4 3 5 Table 8 2 Heating Performance DX Cooling Only and Heat Pump Units with Optional Hot Water Coil Hot Water 180ºF Inlet 160ºF Outlet Entering Air Heating Capacity Flowrate Pressure Drop Model DB ºF 50 RH BTU h GPM PSI 50 46 389 4 8 1 3 CSD CSH 18 60 42 598 4 4 1 1 70 38 746 4 0 0 9 50 50 279 5 3 1 ...

Page 9: ...H BTU h GPM PSI 50 28 389 3 0 11 0 CCW2 8 60 25 903 2 7 9 4 70 23 605 2 5 8 0 50 33 471 3 5 4 6 CCW2 12 60 30 715 3 2 4 0 70 27 995 2 9 3 4 50 60 388 6 3 5 7 CCW 18 60 55 127 5 8 4 8 70 49 706 5 2 4 0 50 65 350 6 8 6 5 CCW 20 60 59 887 6 3 5 6 70 54 118 5 7 4 7 50 99 476 10 4 10 1 CCW 33 60 91 494 9 6 8 8 70 82 986 8 7 7 4 50 114 225 11 9 13 0 CCW 36 60 105 132 11 0 11 2 70 95 896 10 0 9 5 Notes 1...

Page 10: ... 2 3 4 10 11 16 19 9 16 19 1 2 12 9 16 1 7 16 22 15 16 7 8 22 1 2 8 13 16 11 5 16 4 11 16 3 11 16 2 5 8 O 5 3 16 6 1 2 5 1 8 3 3 4 2 1 16 2 5 8 A A VIEW A A 9 13 16 1 1 8 2 3 4 5 7 8 9 5 10 6 1 CW Inlet 2 CW Outlet 3 HW Coil Inlet Optional 4 HW Coil Outlet Optional 5 Branch Duct Opening x3 6 Fresh Air Intake x2 7 Pump Inspection Port 8 Condensate Drain 9 Control Panel 10 Mounting Bracket 1 2 3 4 3...

Page 11: ...6 31 3 8 28 9 16 12 9 16 1 13 16 4 5 8 6 8 5 8 1 5 8 5 5 16 7 3 4 2 3 4 2 3 4 4 7 8 4 15 16 32 5 16 5 3 8 3 3 16 1 5 16 3 8 13 16 8 11 16 11 13 16 3 1 8 7 13 16 2 3 4 VIEW A A A A 2 5 1 4 10 5 6 7 8 9 3 5 3 8 1 CW Coil Inlet 2 CW Coil Outlet 3 HW Coil Inlet Optional 4 HW Coil Outlet Optional 5 Fresh Air Intake x3 6 Branch Duct Opening x4 7 Pump Inspection Port 8 Condensate Drain 9 Control Panel 10...

Page 12: ...1 1 2 2 5 8 28 11 16 12 9 16 28 9 16 1 7 8 43 1 2 7 8 8 13 16 19 5 8 12 7 16 6 3 8 3 5 8 3 3 8 3 6 4 5 8 7 3 16 2 3 16 4 3 4 7 9 16 9 13 16 1 5 8 4 7 8 2 3 4 2 3 4 3 1 8 9 13 16 2 3 4 5 10 2 5 4 3 1 6 7 9 8 1 CW Coil Inlet 2 CW Coil Outlet 3 HW Coil Inlet Optional 4 HW Coil Outlet Optional 5 Fresh Air Intake x3 6 Branch Duct Opening x4 7 Pump Inspection Port 8 Condensate Drain 9 Control Panel 10 M...

Page 13: ...3 4 1 5 8 2 3 4 4 7 8 3 7 16 A A VIEW A A 6 7 8 9 5 5 1 2 4 3 10 1 DX Suction Line 2 DX Liquid Line 3 HW Coil Inlet Optional 4 HW Coil Outlet Optional 5 Fresh AIr Intake x3 6 Branch Duct Opening x4 7 Pump Inspection Port 8 Condensate Drain 9 Control Panel 10 Mounting Bracket 31 3 8 1 7 8 28 9 16 12 9 16 28 11 16 32 3 8 4 3 4 11 5 8 2 5 8 37 37 11 16 Figure 13 1 Dimensions Medium Chassis Model CSD ...

Page 14: ...15 15 3 1 8 2 3 4 9 13 16 VIEW A A A A 8 13 16 2 7 8 2 7 8 4 7 8 6 5 16 4 7 16 2 7 8 3 1 2 4 7 8 6 7 16 1 2 3 4 9 7 8 6 10 5 5 43 1 2 44 7 16 1 DX Suction Line 2 DX Liquid Line 3 HW Coil Inlet Optional 4 HW Coil Outlet Optional 5 Fresh AIr Intake x3 6 Branch Duct Opening x4 7 Pump Inspection Port 8 Condensate Drain 9 Control Panel 10 Mounting Bracket Figure 14 1 Dimensions Large Chassis Model CSD ...

Page 15: ...n in 3 4 3 4 3 4 3 4 3 4 Liquid in 3 8 3 8 3 8 3 8 3 8 Condensate ID in 3 8 3 8 3 8 3 8 3 8 Filtration Type Wire Framed Periframe Quantity 2 2 3 3 3 Arrestance 80 80 80 80 80 Condensate Pump Maximum Head in 30 30 30 30 30 Nominal Flowrate gpm 0 1 0 1 0 1 0 1 0 1 Options Electric Heating Capacity kW 3 0 3 0 5 0 5 0 5 0 HW Heating Capacity 5 BTU h 38 746 41 993 56 609 59 600 64 268 HW Coil Connectio...

Page 16: ...8 7 8 7 8 7 8 7 8 Chilled Water Outlet in 5 8 5 8 7 8 7 8 7 8 7 8 Condensate ID in 3 8 3 8 3 8 3 8 3 8 3 8 Filtration Type Wire Framed Periframe Quantity 1 1 2 2 3 3 Arrestance 80 80 80 80 80 80 Condensate Pump Maximum Head in 30 30 30 30 30 30 Nominal Flowrate gpm 0 1 0 1 0 1 0 1 0 1 0 1 Options Electric Heating Capacity kW 1 5 1 5 3 0 3 0 5 0 5 0 HW Heating Capacity 2 BTU h 13 799 N A 29 258 30 ...

Page 17: ...Color Champagne Dimensions Weights Height includes Fan Guard in 28 28 28 28 30 Width in 23 23 23 29 29 Depth in 23 23 23 29 29 Weight lb 97 129 131 145 173 Compressor Type Rotary Recip Recip Recip Recip Crankcase Heater Fitted No No No No No Condenser Coil Construction Plate Fin Microchannel Plate Fin Microchannel Plate Fin Microchannel Plate Fin Microchannel Plate Fin Microchannel Connections 1 S...

Page 18: ... Champagne Dimensions Weights Height includes Fan Guard in 28 32 36 40 40 Width in 34 34 34 34 34 Depth in 34 34 34 34 34 Weight lb 172 184 196 208 208 Compressor Type Scroll Recip Recip Recip Scroll Crankcase Heater Fitted No Yes Yes Yes No Condenser Coil Construction Round Tube Plate Fin Round Tube Plate Fin Round Tube Plate Fin Round Tube Plate Fin Round Tube Plate Fin Connections 1 Suction in ...

Page 19: ...MCA A 1 5 2 0 2 8 Recommended Fuse A 10 10 10 1 Standard Unit fitted with optional electric heating elements Available with 230V model units only 2 Standard unit fitted with optional booster transformer for connection to a 115V electrical supply Electric heat not available in conjunction with this option Table 19 2 Electrical Data Condensers for DX Cooling Only Units Cassette Unit CSD 18 CSD 24 CS...

Page 20: ... Minimum recommended overcurrent protection Table 20 2 Sound Data Ceiling Cassette Units MERCER TABLE Models Fan Speed SPL dBA 1 Sound Pressure Frequency Spectrum dB 1 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz High 29 37 37 33 29 21 14 10 CCW2 8 Med 26 34 34 30 24 15 12 10 Low 22 31 29 25 17 8 10 8 High 35 42 41 38 35 28 21 12 CCW2 12 Med 32 38 39 36 32 24 16 10 Low 29 37 37 33 29 21 14...

Page 21: ... 21 1 Sound Data Condensers for DX Cooling Only and Heat Pump Units Model Units Cooling Heating YCJD18 dBA 75 YCJD24 dBA 76 YCJD30 dBA 76 YCJD36 dBA 76 YCJD42 dBA 76 YHJD18 dBA 70 1 70 9 YHJD24 dBA 75 8 75 0 YHJD30 dBA 74 7 74 8 YHJD36 dBA 76 5 76 5 YHJD42 dBA 72 0 76 0 Rated in accordance with ARI 270 95 standards ...

Page 22: ...nly The unit contains enough refrigerant for matching indoor coils and 15 feet of interconnecting piping The small base dimension means less space is required on the ground or roof Top Discharge The warm air from the top mounted fan is blown up and away from the structure and any landscaping This allows compact location on multi unit applications Low Operating Sound Level The upward air flow carri...

Page 23: ...wiring connections Available in sweat connect models only The unit contains enough refrigerant for matching indoor coils and 15 feet of interconnecting piping The small base dimension means less space is required on the ground or roof Top Discharge The warm air from the top mounted fan is blown up and away from the structure and any landscaping This allows compact location on multi unit applicatio...

Page 24: ...it Technical Manual AIR 8 105 5 Ceiling Cassette Commercial Products Group Modine Manufacturing Company 1500 DeKoven Avenue Racine WI 53403 2552 Phone 1 866 823 1631 toll free Fax 1 800 204 6011 www airedaleusa com Modine Manufacturing Company 2012 Litho in USA ...

Reviews: