Ceiling Cassette
The SLIMLINE PERFORMER Ceiling Cassette – Ductless Mini-Split
19
Technical Manual : AIR 8-105.5
Table 19.1 – Electrical Data – Ceiling Cassettes
Units
Model Size
2/8 & 2/12
18, 20, & 24
30, 33, 36, & 42
Chassis Size
Small (2 x 2)
Medium (3 x 3)
Large (3 x 4)
Standard Unit Data
Power Supply
208-230V/1Ph/60Hz
208-230V/1Ph/60Hz
208-230V/1Ph/60Hz
Full Load Amps
A
0.65
0.85
1.3
Minimum Circuit Amps (MCA)
A
0.74
0.99
1.4
Recommended Fuse
A
10
10
10
With Optional Electric Heat (1)
Power Supply
208-230V/1Ph/60Hz
208-230V/1Ph/60Hz
208-230V/1Ph/60Hz
Electric Heat Capacity
kW
1.5
3.0
5.0
Full Load Amps
A
7.2
13.9
23.1
Minimum Circuit Amps (MCA)
A
8.9
19.3
28.8
Recommended Fuse with Heat
A
15
20
30
With Optional Booster Xfmr (2)
Power Supply
115V/1Ph/60Hz
115V/1Ph/60Hz
115V/1Ph/60Hz
Full Load Amps
A
1.3
1.7
2.5
Minimum Circuit Amps (MCA)
A
1.5
2.0
2.8
Recommended Fuse
A
10
10
10
(1) Standard Unit fitted with optional electric heating elements. Available with 230V model units only.
(2) Standard unit fitted with optional booster transformer for connection to a 115V electrical supply. Electric heat not available in
conjunction with this option.
Table 19.2 – Electrical Data – Condensers for DX Cooling Only Units
Cassette Unit
CSD 18
CSD 24
CSD 30
CSD 36
CSD 42
Units
Condenser Model
YCJD18 YCJD24
YCJD30
YCJD36
YCJD42
Standard Data
Power Supply
208-230V/1Ph/60Hz
MCA
A 9.8 12.4 14.7 17.9 21.5
Maximum Overcurrent Device Amps (1)
A
15
20
25
30
35
Minimum Overcurrent Device Amps (2)
A
15
15
15
20
25
Compressor
Rated Load Amps (RLA)
A
7.4
9.3
10.6
13.1
16.0
Locked Rotor Amps (LRA)
A
40
43
54
74
84
Condenser Fan
Rated Load Amps (RLA)
A
0.5
0.8
1.4
1.5
1.5
Rated
Horsepower
hp
1/12 1/8 1/4 1/4 1/4
(1) Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.
(2) Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.