Therm-X MVHRU HR95
Technical Manual
Page 29 of 59
Version 2.4, 25/09/2020
DX
Heating
Unit
Type
Air
Volume
[m
3
.h
-1
]
Air
Volume
[m
3
.s
-1
]
Without Heat Recovery
With Heat Recovery
Air On
[
o
C]
Air Off
[
o
C]
Capacity
[kW]
Fluid Pd
[kPa]
Air On
[
o
C]
Air Off
[
o
C]
Capacity
[kW]
Fluid Pd
[kPa]
HR95-080 V
735
0.20
-5.0
27.1
7.9
6
17.4
34.7
4.3
2.0
HR95-150 V
1420
0.39
-5.0
25.9
14.7
13
17.3
34.0
8.0
5.0
HR95-250 V
1820
0.51
-5.0
26.9
19.5
5
17.2
34.5
10.6
2.0
HR95-350 V
3110
0.86
-5.0
27.3
33.7
6
17.1
34.8
18.4
2.0
HR95-450 V
3295
0.92
-5.0
28.3
36.8
8
17.2
35.4
20.0
3.0
HR95-550 V
4460
1.24
-5.0
29.0
50.8
6
17.2
35.7
27.7
2.0
HR95-080 H
600
0.17
-5.0
28.6
6.7
4
17.4
35.6
3.7
1.0
HR95-150 H
1330
0.37
-5.0
26.4
14.0
9
17.1
34.3
7.7
3.0
HR95-250 H
2085
0.58
-5.0
27.5
22.7
11
16.9
34.8
12.5
4.0
HR95-350 H
3650
1.01
-5.0
27.8
40.1
20
17.2
35.1
21.9
7.0
PLEASE NOTE
-
Heat recovery calculated based on the following conditions:
-
Ambient: -5
o
C / 90% RH
-
Room: 21
o
C / 50% RH
-
Coil capacity calculated based on the following conditions:
-
Air density: 1.2 kg.m
-3
-
Condensing: 45
o
C
-
For accurate coil performance data please request a detailed software selection
Cooling
Unit
Type
Air
Volume
[m
3
.h
-1
]
Air
Volume
[m
3
.s
-1
]
Without Heat Recovery
With Heat Recovery
Air On
[
o
C]
Air Off
[
o
C]
Capacity
[kW]
Fluid Pd
[kPa]
Air On
[
o
C]
Air Off
[
o
C]
Capacity
[kW]
Fluid Pd
[kPa]
HR95-080 V
735
0.20
28.0
16.7
4.0
12.0
24.6
15.7
3.5
10.0
HR95-150 V
1420
0.39
28.0
17.0
7.5
26.0
24.7
15.9
6.7
21.0
HR95-250 V
1820
0.51
28.0
16.6
10.0
9.0
23.8
15.4
8.3
6.0
HR95-350 V
3110
0.86
28.0
16.3
17.9
12.0
23.9
15.1
15.3
9.0
HR95-450 V
3295
0.92
28.0
15.9
20.0
16.0
23.8
14.7
16.9
12.0
HR95-550 V
4460
1.24
28.0
15.5
28.1
13.0
23.8
14.4
23.9
10.0
HR95-080 H
600
0.17
28.0
15.9
3.6
8.0
24.6
15.0
3.1
6.0
HR95-150 H
1330
0.37
28.0
16.5
7.6
19.0
24.7
15.4
6.7
15.0
HR95-250 H
2085
0.58
28.0
16.1
12.5
24.0
23.9
14.8
10.7
19.0
HR95-350 H
3650
1.01
28.0
16.0
21.6
44.0
23.8
14.8
18.5
33.0
PLEASE NOTE
-
Heat recovery calculated based on the following conditions:
-
Ambient: 28
o
C / 50% RH
-
Room: 24
o
C / 50% RH
-
Coil capacity calculated based on the following conditions:
-
Air density: 1.2 kg.m
-3
-
Evaporating: 7
o
C, Condensing: 45
o
C
-
For accurate coil performance data please request a detailed software selection