Therm-X MVHRU HR95
Technical Manual
Page 28 of 59
Version 2.4, 25/09/2020
WCO
Cooling
Unit
Type
Air
Volume
[m
3
.h
-1
]
Air
Volume
[m
3
.s
-1
]
Without Heat Recovery
With Heat Recovery
Air On
[
o
C]
Air Off
[
o
C]
Capacity
[kW]
Fluid Pd
[kPa]
Air On
[
o
C]
Air Off
[
o
C]
Capacity
[kW]
Fluid Pd
[kPa]
HR95-080 V
735
0.20
28.0
16.2
4.1
11.0
24.6
15.4
3.5
8.0
HR95-150 V
1420
0.39
28.0
17.0
7.1
8.0
24.7
16.2
6.1
6.0
HR95-250 V
1820
0.51
28.0
16.4
9.9
8.0
23.8
15.4
8.1
6.0
HR95-350 V
3110
0.86
28.0
16.1
17.8
11.0
23.9
15.1
14.8
8.0
HR95-450 V
3295
0.92
28.0
16.2
18.4
5.0
23.8
15.2
14.8
4.0
HR95-550 V
4460
1.24
28.0
15.4
27.7
12.0
23.8
14.5
22.8
8.0
HR95-080 H
600
0.17
28.0
15.8
3.5
6.0
24.6
15.1
3.0
5.0
HR95-150 H
1330
0.37
28.0
17.3
6.3
4.0
24.7
16.4
5.3
3.0
HR95-250 H
2085
0.58
28.0
15.3
12.5
6.0
23.9
14.6
10.1
5.0
HR95-350 H
3650
1.01
28.0
15.4
21.7
7.0
23.8
14.7
17.6
5.0
PLEASE NOTE
-
Heat recovery calculated based on the following conditions:
-
Ambient: 28
o
C / 50% RH
-
Room: 24
o
C / 50% RH
-
Coil capacity calculated based on the following conditions:
-
Air density: 1.2 kg.m
-3
-
CHW Flow: 6
o
C, CHW Return: 12
o
C, no glycol
-
For accurate coil performance data please request a detailed software selection