12.
MAINTENANCE
12.1.
MAINTENANCE SCHEDULE
When properly maintained, the life expectancy of the units under normal operating conditions is in excess of
15 years.
We recommend checking and cleaning the unit every six months though this interval should be adapted to the
operating conditions.
It is recommended to thoroughly clean the unit at least once a year.
If it’s not used for a longer period we recommend turning the unit on for one hour every six months.
Item
Check/cleaning
interval
Filter
3 months or less
Motor
6 months
Plate heat exchanger
6 months
Electronic board
1 year
Damper and Actuator
1 year
Electric coil
1 year
Water coils
1 year
Water changeover coil
1 year
Direct expansion coil
1 year
Filters
Check and replace as necessary.
Damper & Actuator
Check that blades can drive freely and that the damper is free of debris.
Heat exchangers
Clean with a brush and soapy solution and rinse with water. Be careful not to damage the fins.
IMPORTANT:
Failure to replace the filters can lead to a reduction on the performance of the equipment and
ultimately to fan failure.
IMPORTANT:
Failure to clean the heat exchangers can lead to a reduction on the performance of the
equipment and ultimately to fan failure.