THERM-X MVHRU IOM
Page 18 of 108
Version 2.2, 18/06/2020
HR95 (Free Standing Vertical MVHR with Plate Heat Exchanger)
Model with electric pre-
heating coil and… with electric post heating coil
Unit
Type
Phase
Voltage
[V]
Frequency
[Hz]
Power Input
[kW]
Full load current
per phase [A]
HR95-080 V
3
400
50
4.50
11.9
HR95-150 V
3
400
50
9.00
18.0
HR95-250 V
3
400
50
14.20
25.3
HR95-350 V
3
400
50
20.00
29.4
HR95-450 V
3
400
50
25.00
36.7
HR95-550 V
3
400
50
32.80
47.3
HR95-080 H
3
400
50
4.50
11.9
HR95-150 H
3
400
50
9.00
18.0
HR95-250 H
3
400
50
14.20
25.3
HR95-350 H
3
400
50
20.00
29.4
Characteristics of the fan electric motor (per fan)
Unit
Type
Phase
Voltage
[V]
Frequency
[Hz]
Power Input
[kW]
Full Load
Current [A]
Speed
[rpm]
Protection
IP
Insulation
class
HR95-080
1
230
50
0.18
1.3
2800
44
B
HR95-150
1
230
50
0.46
3.1
2600
54
B
HR95-250
1
230
50
0.50
3.2
1970
54
B
HR95-350
3
400
50
1.00
1.8
2140
54
F
HR95-450
3
400
50
1.00
1.8
2140
54
F
HR95-550
3
400
50
1.62
2.5
1750
54
B
Electric post heating coil
Unit
Type
Phase
Voltage
[V]
Frequency
[Hz]
Power Input
[kW]
HR95-080 V
1
230
50
1.40
HR95-150 V
1
230
50
2.70
HR95-250 V
3
400
50
4.80
HR95-350 V
3
400
50
6.40
HR95-450 V
3
400
50
7.60
HR95-550 V
3
400
50
10.60
HR95-080 H
1
230
50
1.40
HR95-150 H
1
230
50
2.70
HR95-250 H
3
400
50
4.80
HR95-350 H
3
400
50
6.40