![AIREDALE Barkell Therm X HR85 Installation, Operation And Maintenance Manual Download Page 20](http://html.mh-extra.com/html/airedale/barkell-therm-x-hr85/barkell-therm-x-hr85_installation-operation-and-maintenance-manual_2876564020.webp)
THERM-X MVHRU IOM
Page 20 of 108
Version 2.2, 18/06/2020
HR85 (Free Standing MVHR with Rotary Heat Exchanger)
Models without electric pre-
heating coil and… without coil / with water heating coil / with WCO coil / with
DX coil
Unit
Type
Phase
Voltage
[V]
Frequency
[Hz]
Power Input
[kW]
Full load current
per phase [A]
HR85-070
1
230
50
0.60
3.9
HR85-100
1
230
50
1.15
6.7
HR85-150
1
230
50
1.20
7.1
HR85-200
1
230
50
1.70
7.7
HR85-300
3
400
50
2.20
4.4
HR85-450
3
400
50
3.70
6.7
HR85-550
3
400
50
3.70
6.7
HR85-750
3
400
50
5.70
9.9
HR85-900
3
400
50
7.20
12.1
HR85-12k
3
400
50
11.70
19.5
Models with electric post heating coil
Unit
Type
Phase
Voltage
[V]
Frequency
[Hz]
Power Input
[kW]
Full load current
per phase [A]
HR85-070
1
230
50
2.60
12.6
HR85-100
3
400
50
4.15
11.1
HR85-150
3
400
50
5.65
13.2
HR85-200
3
400
50
9.20
18.2
HR85-300
3
400
50
11.20
17.4
HR85-450
3
400
50
18.70
28.0
HR85-550
3
400
50
27.80
41.6
HR85-750
3
400
50
35.70
52.9
HR85-900
3
400
50
36.00
53.7
HR85-12k
3
400
50
43.70
65.7
Fan electric motor (per fan)
Unit
Type
Phase
Voltage
[V]
Frequency
[Hz]
Power Input
[kW]
Full Load
Current [A]
Speed
[rpm]
Protection
IP
Insulation
class
HR85-070
1
230
50
0.20
1.2
2650
44
B
HR85-100
1
230
50
0.46
2.8
2600
54
B
HR85-150
1
230
50
0.46
2.8
2600
54
B
HR85-200
1
230
50
0.72
3.1
2800
54
B
HR85-300
3
400
50
1.00
1.6
2580
54
B
HR85-450
3
400
50
1.70
2.6
2600
54
B
HR85-550
3
400
50
1.85
2.9
2180
54
F
HR85-750
3
400
50
2.73
4.2
2040
54
F
HR85-900
3
400
50
3.45
5.3
1910
55
F
HR85-12k
3
400
50
5.70
9.0
2250
55
F