HRFL2 (Ceiling Void MVHR with Plate Heat Exchanger)
Fan electric motor (per fan)
Electric post heating coil
Unit
Type
Phase
Voltage
[V]
Frequency
[Hz]
Power Input [kW]
HRFL2-040
1
230 V
50 Hz
0.80
HRFL2-070
1
230 V
50 Hz
1.40
HRFL2-150
1
230 V
50 Hz
2.70
HRFL2-200
3
400 V
50 Hz
4.80
Electric pre heating coil
Unit
Type
Phase
Voltage
[V]
Frequency
[Hz]
Power Input [kW]
HRFL2-040
1
230 V
50 Hz
1.40
HRFL2-070
1
230 V
50 Hz
2.70
HRFL2-150
3
400 V
50 Hz
5.30
HRFL2-200
3
400 V
50 Hz
7.20
Unit
Type
Phase
Voltage
[V]
Frequency
[Hz]
Power Input
[kW]
FLC
[A]
Speed
[rpm]
Protection IP
Insulation
class
HRFL2-040
1
230 V
50 Hz
0.12
1.10
3640
54
B
HRFL2-070
1
230 V
50 Hz
0.17
1.25
2530
44
B
HRFL2-150
1
230 V
50 Hz
0.46
2.80
2600
54
B
HRFL2-200
1
230 V
50 Hz
0.50
3.15
1890
54
B