background image

506320-01

Issue 1012

     Page  5  of   10

Electrical Connections

Be sure to check all local codes to determine that the unit

is installed in accordance with local requirements.  Consult
the National Electric Code for wire size requirements.  Use
60

/

 C  or higher copper wires only.  Always provide ground

connections to the outdoor unit.  Power supply must agree
with rating on unit nameplate.

Provide line voltage power supply to unit from a properly

sized disconnect switch.  Route power and ground wires
from disconnect switch to unit.  Line voltage connections
are made at the line side of the contactor in the control box
of the outdoor unit.  Follow the  wiring diagram attached to
inside of the access panel.

Proper circuit protection recommendations are  indicated

on Unit Rating Plate. Time delay fuses are required to
prevent blowing due to starting current (the current in rush
when equipment starts is referred to as the Locked Rotor
Amps or (LRA). 

Remove access panel to gain access to unit wiring.

Extend wires from disconnect through power wiring hole
provided and into unit control box.  Flexible conduit is
required for the swing out control box feature.

Connect ground wire to ground connection in control box

for safety.  Connect power wiring to contactor.

High voltage power connections to 3-phase models is

made to "Pig Tail" leads with field supplied splice
connectors.

Control Wiring

The control voltage is 24 Vac. NEC Class I insulated 18

AWG is required for control wiring.  For lengths longer than
150 feet, contact your local distributor for technical service.

Ensure the room thermostat is properly installed per

instructions shipped with room thermostat.  Generally the

thermostat should not be exposed to sunlight, drafts or
vibration and should not be mounted on exterior walls.

Low voltage connections should be in accordance to the

wiring diagram.

Typical Low Voltage Connection

Start-Up Procedure

1.

Close electrical disconnects to energize system.

2.

Set room thermostat at desired temperature.  Be
sure set point is below indoor ambient temperature.

3.

Set the system switch of the thermostat on COOL
and fan switch for continuous operation (ON) or
AUTO, as desired.

4.

Adjust refrigerant charge per "Adjusting Charge"
section.

Adjusting Charge

Factory charge is shown on the rating label located on

the access panel.

All units are  factory charged for 15 feet of

connecting line set. 

  Charge should be adjusted for line

set lengths other than 15 feet.  For line sets shorter than 15
feet in length, remove charge.  For line sets longer than 15
feet, add charge.  Oil charge is sufficient for all line lengths.

Before final adjustment is made to the refrigerant charge,

check for proper indoor airflow.  Recommended airflow is

350-450 CFM per ton

 (12,000 Btuh) through a 

wet coil

.

Refer to indoor unit instructions for methods of determining
air flow and blower performance.

ELECTRICAL SHOCK HAZARD!

Turn OFF electric power before connecting unit,
performing any maintenance or removing
panels or doors.  More than one disconnect
may be required to turn off all power.

FAILURE TO DO SO COULD RESULT IN BODILY
INJURY OR DEATH.

. . . .

The unit cabinet must have an uninterrupted or
unbroken ground.  The ground must be installed in
accordance with all electrical codes.  Failure to follow
this warning can result in an injury, fire, or death.

Refrigeration Charge Adjustment

Liquid Line Diameter

Oz. Per Linear Foot 

3/8"

.6

Low voltage wiring must be separated from high
voltage wiring.

Summary of Contents for 4AC13 Series

Page 1: ...IT SYSTEM AIR CONDITIONER INSTALLATION START UP INSTRUCTIONS HOMEOWNERS INFORMATION MANUAL TABLE OF CONTENTS These units are designed for use in residential and commercial type buildings Heat Pumps are sensitive to indoor units and may only be installed with combinations listed in the Air Conditioning and Refrigeration Institute ARI Directory of Certified Products Refer to http www ahridirectory o...

Page 2: ...approved indoor unit outdoor unit contains system refrigerant charge for operation with indoor unit of the same size when connected by 15 ft of field supplied tubing For proper unit operation check refrigerant charge using charging information located on control box cover IMPORTANT Maximum liquid line size is 3 8 in O D for all residential applications including long lines Outdoor Section Zoning o...

Page 3: ... DO NOT LOCATE THE UNIT On brick concrete blocks or unstable surfaces Near clothes dryer exhaust vents Near sleeping area or near windows Under eaves where water snow or ice can fall directly on the unit with clearance less than 2 ft from a second unit with clearance less than 4 ft on top of unit Indoor Coil Piston Selection The outdoor section must be matched to a factory approved indoor section ...

Page 4: ...e a refrigerant leak detector to check all joints The system may also be checked for leaks using a halide torch or pressure and soapy solution After completion of leak check relieve all pressure from system before evacuation Evacuating And Charging Instructions These outdoor units are pre charged at the factory with adequate refrigerant to handle 15 feet of refrigerant tubing 1 Connect the vacuum ...

Page 5: ...ns shipped with room thermostat Generally the thermostat should not be exposed to sunlight drafts or vibration and should not be mounted on exterior walls Low voltage connections should be in accordance to the wiring diagram Typical Low Voltage Connection Start Up Procedure 1 Close electrical disconnects to energize system 2 Set room thermostat at desired temperature Be sure set point is below ind...

Page 6: ... low and add charge if superheat is high Units with Indoor TXV Units installed with cooling mode TXV require charging with the subcooling method 1 Operate unit a minimum of 10 minutes before checking charge 2 Measure liquid service valve pressure by attaching an accurate gage to service port Determine saturation temp from T P chart 3 Measure liquid line temperature by attaching an accurate thermis...

Page 7: ...506320 01 Issue 1012 Page 7 of 10 A C SINGLE PHASE WIRING DIAGRAM ...

Page 8: ...ees can be drawn into coils by movement of the air Clogged condenser coils will lower the efficiency of your unit and could cause damage to the condenser Periodically debris should be brushed from the condenser coils Use a soft bristle brush with light pressure only DO NOT damage or bend condenser coil fins Damaged or bent fins may affect unit operation Painted Surfaces For maximum protection of t...

Page 9: ...506320 01 Issue 1012 Page 9 of 10 NOTES ...

Page 10: ...506320 01 Issue 1012 Page 10 of 10 NOTES ...

Reviews: