background image

506320-01

Issue 1012

     Page  4  of   10

Installation Of Line Sets

DO NOT fasten liquid or suction lines in direct contact

with the floor or ceiling joist.  Use an insulated or
suspension type of hanger.  Keep both lines separate, and
always insulate the suction line.  Long liquid line runs (30
feet or more) in an attic will require insulation.  Route
refrigeration line sets to minimize length.

DO NOT let refrigerant lines come in direct contact with

foundation.  When running refrigerant lines through the
foundation or wall, openings should allow for a sound and
vibration absorbing material to be placed or installed
between tubing and foundation.  Any gap between
foundation or wall and refrigerant lines should be filled with
a vibration damping material.

Before making braze connections, be sure all joints are

clean.  Before heat is applied for brazing, dry nitrogen
should be flowing through the tubing to prevent oxidation
and scale formation on the inside of the tubing.

The following is the recommended method for making

braze connections at the refrigerant line connections:

1.

Debur and clean refrigerant tube end with emery
cloth or steel brush.

2.

Insert tubing into swage fitting connection.

3.

Wrap wet rags over valves to protect from heat.

4.

Allow dry nitrogen to flow through refrigerant lines.

5.

Braze joint, using a suitable brazing alloy for copper
to copper joints.

6.

Quench the joint and tubing with water using a wet
rag.  Leave rag on fitting body and re-wet with water
to help cool area.

Leak Check

Refrigeration lines and indoor coil must be checked for

leaks after brazing and before evacuation.  The
recommended procedure is to apply a trace amount of
vapor refrigerant (approximately two ounces or 3 psig) into
the line set and indoor coil, then pressurize with 150 psig
of dry nitrogen.  Use a refrigerant leak detector to check all
joints.  The system may also be checked for leaks using a
halide torch or pressure and soapy solution.  After
completion of leak check, relieve all pressure from system
before evacuation.

Evacuating And Charging Instructions

These outdoor units are pre-charged at the factory with

adequate refrigerant to handle 

15 feet

 of refrigerant tubing.

1.

Connect the vacuum pump to the center hose of the
manifold gauge set, the low-pressure manifold gauge
to the vapor service valve and the high pressure
manifold gauge to the liquid service valve.

2.

The valves should be kept in the "front seated"
(closed) position.  This will allow evacuation of the
refrigeration lines and the indoor coil, without
disturbing the factory charge in the outdoor unit.

3.

Follow the vacuum pump manufacturer's
instructions.  Allow the pump to operate until the
system has been evacuated down to 300 microns.
Allow the pump to continue running for an additional
15 minutes.  Turn OFF the pump and leave the
connections secured to the two (2) service valves.
After 5 minutes, if the system fails to hold 1000
microns or less, check all connections for tight fit and
repeat the evacuation procedure.

4.

Isolate the vacuum pump from the system by closing
the shutoff valves on the gauge-set.  Disconnect the
vacuum pump.

5.

After evacuation of the connecting lines, remove the
service valve cap and fully insert the hex wrench into
the stem.  A back-up wrench is required on the valve
body to open the valve stem.  Back-out
counterclockwise until the valve stem just touches
the coined edge.

Replace service valve cap and torque to 8-11 ft-lb on 3/8"

valves; 12-15 ft-lb on 3/4" valves; 15-20 ft-lb on 7/8" valves.

It is unlawful to release refrigerants into the
atmosphere.

If ANY refrigerant tubing is buried, provide a 6 inch
vertical rise at service valve.  Refrigerant tubing
lengths up to 36 inches may be buried without further
special consideration.  For lengths above 36 inches,
consult your local distributor.

Summary of Contents for 4AC13 Series

Page 1: ...IT SYSTEM AIR CONDITIONER INSTALLATION START UP INSTRUCTIONS HOMEOWNERS INFORMATION MANUAL TABLE OF CONTENTS These units are designed for use in residential and commercial type buildings Heat Pumps are sensitive to indoor units and may only be installed with combinations listed in the Air Conditioning and Refrigeration Institute ARI Directory of Certified Products Refer to http www ahridirectory o...

Page 2: ...approved indoor unit outdoor unit contains system refrigerant charge for operation with indoor unit of the same size when connected by 15 ft of field supplied tubing For proper unit operation check refrigerant charge using charging information located on control box cover IMPORTANT Maximum liquid line size is 3 8 in O D for all residential applications including long lines Outdoor Section Zoning o...

Page 3: ... DO NOT LOCATE THE UNIT On brick concrete blocks or unstable surfaces Near clothes dryer exhaust vents Near sleeping area or near windows Under eaves where water snow or ice can fall directly on the unit with clearance less than 2 ft from a second unit with clearance less than 4 ft on top of unit Indoor Coil Piston Selection The outdoor section must be matched to a factory approved indoor section ...

Page 4: ...e a refrigerant leak detector to check all joints The system may also be checked for leaks using a halide torch or pressure and soapy solution After completion of leak check relieve all pressure from system before evacuation Evacuating And Charging Instructions These outdoor units are pre charged at the factory with adequate refrigerant to handle 15 feet of refrigerant tubing 1 Connect the vacuum ...

Page 5: ...ns shipped with room thermostat Generally the thermostat should not be exposed to sunlight drafts or vibration and should not be mounted on exterior walls Low voltage connections should be in accordance to the wiring diagram Typical Low Voltage Connection Start Up Procedure 1 Close electrical disconnects to energize system 2 Set room thermostat at desired temperature Be sure set point is below ind...

Page 6: ... low and add charge if superheat is high Units with Indoor TXV Units installed with cooling mode TXV require charging with the subcooling method 1 Operate unit a minimum of 10 minutes before checking charge 2 Measure liquid service valve pressure by attaching an accurate gage to service port Determine saturation temp from T P chart 3 Measure liquid line temperature by attaching an accurate thermis...

Page 7: ...506320 01 Issue 1012 Page 7 of 10 A C SINGLE PHASE WIRING DIAGRAM ...

Page 8: ...ees can be drawn into coils by movement of the air Clogged condenser coils will lower the efficiency of your unit and could cause damage to the condenser Periodically debris should be brushed from the condenser coils Use a soft bristle brush with light pressure only DO NOT damage or bend condenser coil fins Damaged or bent fins may affect unit operation Painted Surfaces For maximum protection of t...

Page 9: ...506320 01 Issue 1012 Page 9 of 10 NOTES ...

Page 10: ...506320 01 Issue 1012 Page 10 of 10 NOTES ...

Reviews: