506320-01

Issue 1012

     Page  1  of   10

These instructions must be read and understood completely before attempting installation.

Issue 1012

Safety  Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .     2

Unit  Location  &  Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .     2

Rooftop Installation & Recommendations . . . . . . . . . . . . . . . . . . . .     3

Indoor Coil Piston Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .     3

Refrigeration  Line  Sets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .     3

Installation  of  Line  Sets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .     4

Leak Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .     4

Evacuating  &  Charging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .     4

Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .     5

Control  Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .     5

Start-Up Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .     5

Adjusting  charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .     5

Single  Phase  Wiring  Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . .     7

3  Phase  Wiring  Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .     8

Homeowner's  Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .     9

NOTES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Installation or repairs made by unqualified persons can result in hazards to you and others.  Installation
MUST conform with local building codes or, in the absence of local codes, with the National Electrical Code
NFPA 70/ANSI C1-1993 or current edition and Canadian Electrical Code Part 1 CSA C22.1.

4AC13/14 SPLIT SYSTEM AIR CONDITIONER

INSTALLATION / START-UP INSTRUCTIONS

/HOMEOWNERS INFORMATION MANUAL

TABLE OF CONTENTS

These units are designed for use in residential and commercial type buildings.  Heat Pumps are sensitive to
indoor units and may only be installed with combinations listed in the Air-Conditioning and Refrigeration Institute
(ARI) Directory of Certified Products.  Refer to 

http://www.ahridirectory.org

 .  

After un-crating unit, inspect thoroughly for hidden damage.  If damage is found, notify the transportation
company immediately and file a concealed damage claim.

Improper installation, adjustment, alteration, service or maintenance will void the warranty.  The qualified installer or
agency must use factory-authorized kits or accessories when modifying this products.  Refer to the individual instructions
packaged with the kits or accessories when installing.

NOTE

These instructions are intended as a general guide and do not supersede national, state or local codes in any way.

These instructions must be left with the property owner.

Summary of Contents for 4AC13 Series

Page 1: ...IT SYSTEM AIR CONDITIONER INSTALLATION START UP INSTRUCTIONS HOMEOWNERS INFORMATION MANUAL TABLE OF CONTENTS These units are designed for use in residential and commercial type buildings Heat Pumps are sensitive to indoor units and may only be installed with combinations listed in the Air Conditioning and Refrigeration Institute ARI Directory of Certified Products Refer to http www ahridirectory o...

Page 2: ...approved indoor unit outdoor unit contains system refrigerant charge for operation with indoor unit of the same size when connected by 15 ft of field supplied tubing For proper unit operation check refrigerant charge using charging information located on control box cover IMPORTANT Maximum liquid line size is 3 8 in O D for all residential applications including long lines Outdoor Section Zoning o...

Page 3: ... DO NOT LOCATE THE UNIT On brick concrete blocks or unstable surfaces Near clothes dryer exhaust vents Near sleeping area or near windows Under eaves where water snow or ice can fall directly on the unit with clearance less than 2 ft from a second unit with clearance less than 4 ft on top of unit Indoor Coil Piston Selection The outdoor section must be matched to a factory approved indoor section ...

Page 4: ...e a refrigerant leak detector to check all joints The system may also be checked for leaks using a halide torch or pressure and soapy solution After completion of leak check relieve all pressure from system before evacuation Evacuating And Charging Instructions These outdoor units are pre charged at the factory with adequate refrigerant to handle 15 feet of refrigerant tubing 1 Connect the vacuum ...

Page 5: ...ns shipped with room thermostat Generally the thermostat should not be exposed to sunlight drafts or vibration and should not be mounted on exterior walls Low voltage connections should be in accordance to the wiring diagram Typical Low Voltage Connection Start Up Procedure 1 Close electrical disconnects to energize system 2 Set room thermostat at desired temperature Be sure set point is below ind...

Page 6: ... low and add charge if superheat is high Units with Indoor TXV Units installed with cooling mode TXV require charging with the subcooling method 1 Operate unit a minimum of 10 minutes before checking charge 2 Measure liquid service valve pressure by attaching an accurate gage to service port Determine saturation temp from T P chart 3 Measure liquid line temperature by attaching an accurate thermis...

Page 7: ...506320 01 Issue 1012 Page 7 of 10 A C SINGLE PHASE WIRING DIAGRAM ...

Page 8: ...ees can be drawn into coils by movement of the air Clogged condenser coils will lower the efficiency of your unit and could cause damage to the condenser Periodically debris should be brushed from the condenser coils Use a soft bristle brush with light pressure only DO NOT damage or bend condenser coil fins Damaged or bent fins may affect unit operation Painted Surfaces For maximum protection of t...

Page 9: ...506320 01 Issue 1012 Page 9 of 10 NOTES ...

Page 10: ...506320 01 Issue 1012 Page 10 of 10 NOTES ...

Reviews: