APPENDIX B

TROUBLESHOOTING

Problem: No power to AirCycler® g1

Check common wire connection. “C” must be connected to “C” on the furnace.

Problem: Furnace fan is running constantly

Make sure the thermostat FAN switch is set to AUTO and not ON.

Problem: Central fan does not shut off when AirCycler® g1 is removed from base (when thermostat fan switch is on)

Check wiring - “G” wire from thermostat should be wired to “Gt” on AirCycler® g1. “Gf” on AirCycler® g1 should be

connected to “G” on furnace.

Problem: Blank Display on the AirCycler® g1

Confirm:

1.  The furnace has power

2.  The thermostat is operational

3.  The furnace will call for heat from the thermostat

4.  The fan operates with a fan only signal from the thermostat

5.  The furnace is providing 24 VAC to the  AirCycler® g1

6.  Verify wiring conforms to wiring diagram

7.  Make sure cover is firmly seated on the base

Problem: AirCycler® g1 turns furnace fan on and off, but the motorized damper does not cycle.

Confirm:

1.  The AirCycler® g1 is providing a 24 VAC signal to the motorized damper

2.  The 24 VAC motorized damper is operational by powering directly with a 24 VAC signal

3.  There is continuity in the wiring between the damper and the AirCycler® g1

4.  Confirm damper power switch is in up or automatic position

Problem: A/C turns on during fan cycling calls

Confirm:

1.  Wiring conforms to wiring diagram

2.  The G wire is properly connected

3.  The G wire needs to be interrupted by the  AirCycler® g1

4.  Do not run the G wire in parallel

Technical Support:

1.877.FAN.CONTrol

(1.877.326.2668)

Summary of Contents for g1

Page 1: ...AirCycler g1 Installation User s Guide VENTILATION MADE BREEZY a breeze to install a breeze to use Ventilation Products ...

Page 2: ...here are not enough heating or cooling calls to meet ventilation requirements for the hour the AirCycler g1 will turn on the furnace fan and open the motorized damper until requirements have been met SAFETY CONSIDERATIONS Read and follow manufacturer s instructions carefully Follow all local electrical codes during installation All wiring must conform to local and national electrical codes Imprope...

Page 3: ...ires the central blower used with the AirCycler g1 to use an electronically commutated motor WIRING DIAGRAM Y R W G Y R C W G White OPTIONAL DAMPER Red Blue THERMOSTAT AirCycler g1 AIR HANDLER KEY R 24VAC Power C Common Gt Fan From Thermostat Gf Fan To Furnace V Vent Vnc Normal Closed Vent ...

Page 4: ...if mounted horizontally Air may flow through in either direction although it is recommended to install with the crimped end as the outlet Use care to avoid distorting the damper housing and provide adequate support Upon system start up be sure to set damper power switch to UP or AUTOMATIC position CHOOSE A FRESH AIR LOCATION ASHRAE recommends that the fresh air intake be located at least 10 ft fro...

Page 5: ...t up the AirCycler g1 based on Calculated Time press and hold the DOWN arrow for 10 seconds OPERATING MODE DISPLAY When the AirCycler is in Normal Operation the display will show the percentage of ventilation complete for the current hour If the outside fresh air damper is open the OA icon will show If the thermostat is calling for heat or cool the FAN icon will be illuminated without the ON icon ...

Page 6: ...ation press the UP arrow for yes YS Press MODE to select yes The AirCycler g1 will prompt you to enter the hour you would like the ventilation to begin and the hour you want it to end followed by the current time Set the hour you want ventilation to START Press MODE to advance to the next setting Set the hour you want the ventilation to STOP Press MODE to advance to next setting 2 4 1 SETTING CURR...

Page 7: ...ING OPERATION HOURS If the user does not want the ventilation system to run throughout the day you can set ON time and OFF time Factory default is NO If you are not setting an ON and OFF time press MODE and continue to section 3 4 If you want to set hours of operation press the UP arrow for yes YS Press MODE to select yes The AirCycler g1 will prompt you to enter the hour you would like the ventil...

Page 8: ...ns will show Required CFM set Measured outside air CFM If operating time is enabled Operating Time ON Operating Time OFF For Calculated Time mode the screens will show Outside air time in minutes If operating time is enabled Operating Time ON Operating Time OFF 5 0 SET CURRENT TIME By pressing the MODE key you will cycle through current time of day and will be able to change it if needed See secti...

Page 9: ...CFM N 1 A 0 01 N No of Bedrooms A Square Footage Square Footage No of Bedrooms SOFTWARE VERSION To determine the software version used in your controller press and hold the DOWN arrow for 15 seconds from normal operation The software revision number will be displayed on the screen ...

Page 10: ... fan operates with a fan only signal from the thermostat 5 The furnace is providing 24 VAC to the AirCycler g1 6 Verify wiring conforms to wiring diagram 7 Make sure cover is firmly seated on the base Problem AirCycler g1 turns furnace fan on and off but the motorized damper does not cycle Confirm 1 The AirCycler g1 is providing a 24 VAC signal to the motorized damper 2 The 24 VAC motorized damper ...

Reviews: