![AIC COILMASTER 100 Installation And Maintenance Manual For The Installer And The User Download Page 70](http://html1.mh-extra.com/html/aic/coilmaster-100/coilmaster-100_installation-and-maintenance-manual-for-the-installer-and-the-user_2870753070.webp)
Fig. 23. Cleaning the Combustion Chamber
I-70
G-084383_EN • 03
M
aintenance
Checking and Cleaning the Combustion
Chamber
Conditions:
î
Burner removed, see
“Removing and Install
-
ing the Burner - CM 60 - 70 - 80” on page
I-66
,
or
“Removing and Installing the Burner
- CM 100 - 120” on page
I-68
.
Tools and material:
î
Industrial vacuum cleaner
î
Nylon bristle brush
î
Torch
Check Procedure:
1.
Using a torch, visually check the condition of
the combustion chamber. If it is dirty, clean it.
Cleaning Procedure:
1.
Using a nylon bristle brush, sweep the walls
of the combustion chamber.
2.
Using an industrial vacuum cleaner, remove
all deposits from the combustion chamber
heating surfaces.
OFF
If the burner door insulation plate
is present, do not perform step 3,
as it could damage the insulation
plate.
3.
Pour some clean water to remove any residues.
Follow-on tasks:
1.
Remove and clean condensate trap, refer to
“Cleaning the Condensate Pipe and Trap”
on page
I-61
2.
Install the burner, see
“Removing and In
-
stalling the Burner - CM 60 - 70 - 80” on
page
I-66
,
or
“Removing and Installing
the Burner - CM 100 - 120” on page I-68
.