PRE-HEAT
Pre-heat without electrical heater
a)
MTV1, MTV2 and AUX2 are off.
b)
If Ti1 < 96.8ºF [or 82.4ºF is selected by DIPB-S2 position SW4], then AUX1 is on while indoor fan remains off.
c)
If Ti1 ≥ 100.4ºF [or 86ºF is selected by DIPB-S2 position SW4], then AUX1 is on while indoor fan runs at set
speed.
d)
If the indoor coil temperature sensor is damaged, then the pre-heat time is set for 2 minutes. Indoor fan runs
at set speed.
Pre-heat with electrical heater
a)
Indoor fan will start after the electrical heater has been turned on for 10 seconds.
POST-HEAT
Post-heat with and without electrical heater
a)
AUX1 is off. Electrical heater is turned off.
b)
Indoor fan will stop after the unit has been turned off for 20 seconds.
Over heat protection of indoor coil in post-heat
a)
If Ti1 ≥ 167ºF, then AUX1 is turned off, indoor fan remains on and runs at high speed.
b)
If Ti1 < 158ºF, then AUX1 is turned on, indoor fan remains on and runs at set speed.
c)
If the indoor coil temperature sensor is damaged, then the protection mode will be overridden and the unit
will work according to the pre-heat and post-heat program.
DEHUMIDIFICATION MODE
a)
MTV1, MTV2, AUX1 and heater are always off.
b)
If Tr ≥ 77ºF, then indoor fan and AUX2 will be ON for 3 minutes, and then OFF for 4 minutes.
c)
If 60.8ºF ≤ Tr < 77ºF, then indoor fan and AUX2 will be ON for 3 minutes, and then OFF for 6 minutes.
d)
If Tr < 60.8ºF, then indoor fan and AUX2 will be turned off for 4 minutes.
e)
At the end of the above dehumidification cycle, the system will decide the next dehumidification control
option. Indoor fan will run at low speed throughout the dehumidification process.
AUTOMODE
Not available.