Page 52 of 83
SK2018 PCG(H)-V/P-AECM-001
PRE-HEAT
Pre-heat without electrical heater
a)
If Ti1 < 96.8ºF [or < 82.4ºF is selected by DIPB-S2 position SW4], then MTV1 and AUX1 are turned on, indoor fan
runs at Modbus 310000 setting.
b)
If Ti1 ≥ 100.4ºF [or ≥ 86ºF is selected by DIPB-S2 position SW4], then MTV1 and AUX1 are turned on, indoor fan
runs at set speed.
c)
If the indoor coil temperature sensor is damaged, then the pre-heat time is set for 2 minutes. Indoor fan runs at
set speed.
Pre-heat with electrical heater
a)
If the indoor fan speed ≥ 300rpm, then the electrical heater will turn on.
POST-HEAT
Post-heat without electrical heater
a)
If Ti1 ≥ 100.4ºF, then MTV1 and AUX 1 are off. then indoor fan continues to run at set speed.
b)
If 96.8°F ≤ Ti1 ≤ 100.4°F, then MTV1 and AUX1 are turned off. Indoor fan maintains its original state.
c)
If Ti1 < 96.8ºF, then MTV1 and AUX1 are turned off. Indoor fan runs at Modbus 310000 setting.
d)
If the indoor coil temperature sensor is damaged, then the post-heat time is set for 3 minutes. Indoor fan runs at
set speed.
Post-heat with electrical heater
a)
Indoor fan will run at Modbus 310000 setting before the unit turns off for 20 seconds.
Over-heat protection of indoor coil in post-heat
a)
If Ti1 ≥ 167ºF, then MTV1 and AUX1 are turned off. Indoor fan remains on and runs at high speed.
b)
If Ti1 < 158ºF, then MTV1 and AUX1 are turned on. Indoor fan remains on and runs at set speed.
c)
If the indoor coil temperature sensor is damaged, then the protection mode will be overridden and the unit will
work according to the pre-heat and post-heat program.
DEHUMIDIFICATION MODE
a)
MTV2, AUX1 and heater are always off.
b)
If Tr ≥ 77ºF, then MTV1 and AUX2 will be ON for 3 minutes, and then OFF for 4 minutes.
c)
If 60.8ºF ≤ Tr < 77ºF, then MTV1 and AUX2 will be ON for 3 minutes, and then OFF for 6 minutes.
d)
If Tr < 60.8ºF, then MTV1 and AUX2 will be turned off for 4 minutes.
e)
At the end of the above dehumidification cycle, the system will decide the next dehumidification control option.
Indoor fan will run at low speed throughout the dehumidification process.