29
Ve
ntin
g
For improved indoor air quality, added safety and product per-
formance we recommend direct vent type installations. If non-di-
rect type vent system is used, the requirements for combustion
air must be provided as identified in the National Fuel Gas Code
and, in Canada, CSA B149.1; Canadian Natural Gas and
Propane Installation Code.
Combustion air requirements are determined by whether the fur-
nace is in an open (unconfined) area or in a confined space
such as a closet or small room.
CONFINED AND UNCONFINED SPACES
The below instructions are for U.S. installations only. The terms
Confined Space
and
Unconfined Space
refer to U.S. installa-
tions only. In Canada the proper term to use is
Enclosure
when
specifying that a furnace is installed in a partially enclosed or
fully enclosed room or space. For Canadian installations, to de-
termine combustion air requirements for non-direct vent installa-
tions, the installer must follow CSA B149.1; Canadian Natural
Gas and Propane Installation Code and NOT the below instruc-
tions.
FURNACE LOCATED IN AN UNCON-
FINED SPACE (U.S. INSTALLATIONS)
USING INDOOR AIR FOR COMBUSTION:
An unconfined space must have at least 50 cubic feet for each
1,000 BTUH of total input for all appliances in the space.
Table
6
below specifies minimum space requirements and a few ex-
amples of the room sizes required for different inputs. The sizes
are based on 8-foot ceilings.
If the open space containing the furnace is in a building with
tight construction, outside air may still be required for the fur-
nace to operate and vent properly. Outside air openings should
be sized the same as for a confined space.
FURNACE LOCATED IN A CONFINED
SPACE (U.S. INSTALLATIONS)
A confined space is defined as any space for a given furnace
input rating which is smaller than that which is specified in
Table
6
as minimum for an “
unconfined
” space. If the space is less than
that specified in this table, the space is defined as “
confined
”.
If the space is small enough to be designated as “confined”, it
must have openings into the space which are located in accor-
dance with the requirements set forth in the following subsec-
tions A and B. Size connected to the heated area or to the
outside, and by the input of
ALL
appliances in the space.
If the confined space is within a building with tight construction,
combustion air must be taken from outdoors or from an area
freely communicating with the outdoors.
A. USING INDOOR AIR FOR COMBUSTION:
IMPORTANT:
Air should not be taken from a heated space
with a fireplace, exhaust fan or other device that may pro-
duce negative pressure.
If combustion air is taken from the heated area, the open-
ings must each have at least 100 square inches of free
area. Each opening must have at least one square inch of
free area for each 1,000 BTUH of total input in the space.
Table 7
shows some typical examples of openings required
for combustion air openings required for a confined space.
NON-DIRECT VENT (VERTICAL TERMINATIONS ONLy)
GENERAL VENTING REqUIREMENTS AND
GUIDELINES
!
WARNING
ALL FURNACE INSTALLATIONS MUST COMPLy WITH
THE NATIONAL FUEL GAS CODE, NFPA 54, AND IN
CANADA CSA B149.1; CANADIAN NATURAL GAS AND
PROPANE INSTALLATION CODE, THE NATIONAL FIRE
CODE OF CANADA, AND LOCAL CODES TO PROVIDE
ADEqUATE COMBUSTION AND VENTILATION AIR FOR
THE FURNACE. FAILURE TO DO SO CAN RESULT IN
ExPLOSION, FIRE, PROPERTy DAMAGE, CARBON
MONOxIDE POISONING, PERSONAL INJURy OR DEATH.
TABLE 6: MINIMUM SPACE REQUIREMENTS
FOR UNCONFINED SPACE, NON-DIRECT VENT
TABLE 7: MINIMUM FREE AREA
OPENING REQUIRED FOR A
FURNACE LOCATED IN A
CONFINED SPACE USING
INDOOR AIR FOR COMBUSTION.
!
WARNING
READ AND FOLLOW THE
GENERAL VENTING REQUIRE-
MENTS AND GUIDELINES
OF THIS MANUAL FOR ADDI-
TIONAL VENTING REqUIREMENTS PERTAINING TO ALL
FURNACE INSTALLATIONS (INCLUDING DIRECT AND
NON-DIRECT VENTING). FAILURE TO FOLLOW ALL IN-
STRUCTIONS IN THIS MANUAL CAN RESULT IN EqUIP-
MENT FAILURE, EqUIPMENT DAMAGE, PROPERTy
DAMAGE, PERSONAL INJURy OR DEATH.
Summary of Contents for (-)98VA060M317USA
Page 12: ...Field Conversions FIELD CONVERSIONS 12 ...
Page 13: ...FIELD CONVERSIONS Field Conversions 13 SEE NExT PAGE FOR APPLICABLE CONFIGURATIONS ...
Page 15: ...Field Conversions 15 ...
Page 16: ...Field Conversions ST A1194 68 00 16 ...
Page 17: ...Field Conversions 17 ...
Page 18: ...Field Conversions 18 ...
Page 92: ...92 Diagnostics TABLE 19 R98V FAULT CODES WITH DESCRIPTIONS AND SOLUTIONS ...
Page 93: ...93 TABLE 19 continued R98V FAULT CODES WITH DESCRIPTIONS AND SOLUTIONS Diagnostics ...
Page 94: ...94 Diagnostics TABLE 19 continued R98V FAULT CODES WITH DESCRIPTIONS AND SOLUTIONS ...
Page 95: ...95 TABLE 19 continued R98V FAULT CODES WITH DESCRIPTIONS AND SOLUTIONS Diagnostics ...
Page 96: ...96 Diagnostics TABLE 19 continued R98V FAULT CODES WITH DESCRIPTIONS AND SOLUTIONS ...
Page 97: ...97 TABLE 19 continued R98V FAULT CODES WITH DESCRIPTIONS AND SOLUTIONS Diagnostics ...
Page 98: ...98 Diagnostics TABLE 19 continued R98V FAULT CODES WITH DESCRIPTIONS AND SOLUTIONS ...
Page 99: ...99 TABLE 19 continued R98V FAULT CODES WITH DESCRIPTIONS AND SOLUTIONS Diagnostics ...
Page 100: ...100 Diagnostics TABLE 19 continued R98V FAULT CODES WITH DESCRIPTIONS AND SOLUTIONS ...
Page 101: ...101 TABLE 19 continued R98V FAULT CODES WITH DESCRIPTIONS AND SOLUTIONS Diagnostics ...
Page 105: ...105 FIGURE 67 MODULATING ECM FURNACE WIRING DIAGRAM Troubleshooting ...
Page 106: ...106 ...
Page 107: ...107 ...
Page 108: ...108 CM 0717 ...