103
DIAGNOSING BLOWER MOTOR ISSUES
1. MOTOR POWER AND COMMUNICATIONS IS-
SUES (FAULT CODE “68”)
Is the motor communicating properly with the fur-
nace control? If not, the fault code “68” will be dis-
played any time there is a call for cooling, heating or
continuous fan. To determine the cause of this issue,
follow these steps:
A. Remove the line voltage connector from the
motor. This is the 5-pin connector. With the door
switch closed, verify that there is 115-120VAC be-
tween pins 4 and 5 of the connector (see photos
in Figure 63B). If no line voltage is detected,
check the wiring and correct the issue. Line volt-
age should be present at these pins any time the
furnace is powered. Make sure that the pins of
the connector are fully seated in the housing to
ensure good contact with the connection at the
motor. When voltage is confirmed at these pins,
replace the connector on the motor.
B. Remove the motor control connector from the fur-
nace control at P5 and apply 24VAC to pins 3 & 4
(see photo). With the door switch closed (motor
powered) and 24VAC on pins 3 & 4, the motor
should start operating at 75% of capacity. If the
motor is operating at a good speed, it is likely not
the motor that is the problem. If the motor is not
operating, verify that the control wiring between
the motor and furnace control (to P5) is good and
that all the pins on both ends are fully seated. If
the wiring connections looks good, and the motor
still will not operate, the motor likely needs to be
replaced.
DIAGNOSTICS AND TROUBLESHOOTING
FIGURE 65
LINE VOLTAGE AND LOW VOLTAGE CONNECTIONS TO THE COMMUNICATING MOTOR
A
B
Dia
gn
ost
ics
Summary of Contents for (-)98VA060M317USA
Page 12: ...Field Conversions FIELD CONVERSIONS 12 ...
Page 13: ...FIELD CONVERSIONS Field Conversions 13 SEE NExT PAGE FOR APPLICABLE CONFIGURATIONS ...
Page 15: ...Field Conversions 15 ...
Page 16: ...Field Conversions ST A1194 68 00 16 ...
Page 17: ...Field Conversions 17 ...
Page 18: ...Field Conversions 18 ...
Page 92: ...92 Diagnostics TABLE 19 R98V FAULT CODES WITH DESCRIPTIONS AND SOLUTIONS ...
Page 93: ...93 TABLE 19 continued R98V FAULT CODES WITH DESCRIPTIONS AND SOLUTIONS Diagnostics ...
Page 94: ...94 Diagnostics TABLE 19 continued R98V FAULT CODES WITH DESCRIPTIONS AND SOLUTIONS ...
Page 95: ...95 TABLE 19 continued R98V FAULT CODES WITH DESCRIPTIONS AND SOLUTIONS Diagnostics ...
Page 96: ...96 Diagnostics TABLE 19 continued R98V FAULT CODES WITH DESCRIPTIONS AND SOLUTIONS ...
Page 97: ...97 TABLE 19 continued R98V FAULT CODES WITH DESCRIPTIONS AND SOLUTIONS Diagnostics ...
Page 98: ...98 Diagnostics TABLE 19 continued R98V FAULT CODES WITH DESCRIPTIONS AND SOLUTIONS ...
Page 99: ...99 TABLE 19 continued R98V FAULT CODES WITH DESCRIPTIONS AND SOLUTIONS Diagnostics ...
Page 100: ...100 Diagnostics TABLE 19 continued R98V FAULT CODES WITH DESCRIPTIONS AND SOLUTIONS ...
Page 101: ...101 TABLE 19 continued R98V FAULT CODES WITH DESCRIPTIONS AND SOLUTIONS Diagnostics ...
Page 105: ...105 FIGURE 67 MODULATING ECM FURNACE WIRING DIAGRAM Troubleshooting ...
Page 106: ...106 ...
Page 107: ...107 ...
Page 108: ...108 CM 0717 ...