Operation
26
Europress
4.
Set the test valve (white connection) to position "Normal Opera-
tion".
The pressure in the interstitial space increases, but it must not
exceed 570 mbar!
5.
Set the measurement valve (red connection) to position "Normal
Operation".
The pump must switch off immediately.
Function test of the indicators
Press the "Test" key.
The green LED "Operation", the red LED "Alarm" and the yellow
LED "Service" light and the audible alarm is activated. The au-
dible alarm can be muted by means of the button "Mute".