Mounting
and
commissioning
Europress
21
6.6
Drying filter
Drying filters must be mounted in the suction line in order to dry the
intake air (filters not included, see accessories, chapter 11, page 31).
1
Holder with mounting accesso-
ries
2
Silicon hose
3
Outlet, filtered
4
Filter head, aluminium
5
O ring Ø 54 x 3 NBR
6
SIKU disc 50 µm, dust filter
7
Union nut M 64 x 1.5
8
Drying beads
9
Filter bowl
10
Inlet, not filtered
Fig. 8: Drying filter
1.
Determine the number of drying filters required on the basis of
the table below and fasten them close to the leak detector using
pipe clamps.
For
underground tanks
: 1 x drying filter type TF 220
For
aboveground tanks
(only a
single
aboveground tank may
be connected):
Interstitial space volume
Number of drying filters
up to 300 litres
1 x TF 220
up to 700 litres
2 x TF 220
up to 1000 litres
3 x TF 220
up to 1500 litres
4 x TF 220
up to 1800 litres
5 x TF 220
up to 2200 litres
6 x TF 220
up to 2600 litres
7 x TF 220
up to 3000 litres
8 x TF 220