37
6.1 Power ON
Turn on DC switch.
After LCD lighting, hybrid inverter should be set following Chapter 5.3 at the first time.
When inverter running under normal mode,
Running
indicator will light up(Ref. to Chapter
5.1).
6.2 Power off
Turn off DC switch ( in hybrid inverter) and all extra-breaker.
6.3 Restart
Restart Hybrid inverter, please follow steps as below:
Shutdown the inverter Ref. to Chapter6.2.
Start the inverter Ref. to Chapter 6.1.
7.Maintenance&Trouble Shooting
7.1 Maintenance
Periodically maintenance are necessary, please follow steps as below.
PV connection: twice a year
AC connection(Grid and EPS) : twice a year
Battery connection: twice a year
Earth connection: twice a year
Heat sink: clean with dry towel once a year
7.2 Trouble Shooting
The fault messages are displayed when fault occurs, please check trouble shooting table and find
related solutions.
Fault Code and Trouble Shooting
Fault Type
Code
Name
Description
Recommended Solution
PV Fault
A01
PvConnectFault
PV connection type
different from setup
1. Check PV modules connection
2. Check
PV Mode
setup Ref.
Chapter 5.3.
A02
IsoFault
ISO check among PV
panels/ wires and
ground is abnormal.
1. Check PV modules wires, those
wires are soaked or damaged, and
then carry out rectification.
2. If the fault occurs continuously
and frequently, please ask help for
local distributors.
Summary of Contents for AF3.6K-DH
Page 14: ...13 4 2 Mounting ...
Page 17: ...16 Lithium ...
Page 19: ...18 ...
Page 22: ...21 Pin BAT NCT CAN 1 TEP T 2 TEP G 3 CAN H 4 CAN L ...
Page 27: ...26 EPS Connection Generator Connection ...
Page 49: ...48 8 Specifications Hybrid Inverter ...
Page 50: ...49 ...
Page 51: ...50 ...
Page 52: ...Building 7 No 333 Wanfang Rd Minhang District Shanghai China 201112 Version HH1004 01 ...