3
Installation
Installing brackets (see Fig. 1 – 4)
►
Check fasteners for damage.
►
Note the number of fastening points (see
Tab. A1 and A2).
–
Determine the minimum number each
by wall material for requirements class
1 – 3.
►
Note the number of fastening points (see
Fig. B).
►
Prepare tools.
►
Mark holes to be drilled.
–
Refer to the radiator's operating and
installation instructions for the radiator
dimensions.
►
Drill holes and seat dowel.
–
Do not percussion-drill into Poroton
brick.
–
Seat dowel into the wall up to the
flange.
►
Hand-screw the brackets on.
►
Align brackets horizontally and vertically
and tighten screws.
WARNING
Requirement class 3
►
Install wall rail for steel panel ra-
diators with shift restraint (Item No.
ZK00800001) only.
►
Follow the further installation steps,
see installation instructions for shift
restraint.
Installing and securing the radiator
(see Fig. 5 – 8)
►
Pretension the brackets.
►
Place the radiator with the bottom edge on
the bracket foot and slide over the sound
insulation into the track, upright and press
in at the top.
►
Check whether the spring mechanism has
engaged on all brackets (visual inspection).
►
Ensure safeguard against shifting and dig-
ging due to tightening of the top screw.
EN – Installation instructions
Permissible use
The brackets may only be used to install Kermi
steel panel radiators.
Any other use is contrary to its intended pur
-
pose and therefore not permissible.
Safety instructions
►
Read these instructions thoroughly prior to
installation.
DANGER
Life-threatening situation!
►
Check the condition of the supply lines
(electricity, gas, water).
►
Do not drill into any lines.
WARNING
Risk of injury from spring mechanism!
Each bracket is pretensioned by a spring
mechanism that engages when the radiator
is actuated.
►
Pretension brackets only after installa
-
tion on the wall.
►
Do not take hold of the pretensioned
brackets.
WARNING
Personal injury and material damage!
►
Check substrate for load-bearing capac-
ity. Take the
filled
weight of the radia-
tor and possible additional loads into ac-
count (see manufacturer's data).
►
Check fasteners for applicability and tai
-
lor them to the structural situation.
►
Special requirements, e.g. for public
buildings (schools or the like), must be
taken into into account.
Disposal
►
Packaging and any parts that are not need
-
ed should be recycled or disposed of prop
-
erly. Observe local regulations.
Wall spacing
The space from the wall to the backside of the
heater is 34 mm.
Summary of Contents for Kermi ZB02970017
Page 13: ...13 EL Kermi 34 mm 1 4 A1 A2 1 3 Poroton 3 ZK00800001 5 8...
Page 14: ...14 RU Kermi 34 1 4 A1 A2 1 3 3 ZK00800001 5 8...
Page 15: ...15 ZH Kermi 34 mm 1 4 A1 A2 1 3 B 3 ZK00800001 5 8...
Page 16: ...16 3 10000800KZ 8 5 RA imreK 2A 1A 3 1 B RA 1000 RA imreK 43 4 1...
Page 17: ...17 AF imreK 43 4 1 2A 1A 3 1 B AF 1 3 10000800KZ 8 5...