Before Installation 

Please  read  these  instructions  carefully  and  keep  for  future 
reference.   
The  information  in  this  document  is  subject  to  change  without 
notice. For updates please refer to our website. 
 

CAUTION

!

 

Do not use the products outside the rated power supply voltage 

range  specified  in  the  Specifications.  It  may  cause  a  fire  or 
damage to equipment. 

Do not disassemble, repair, or modify the products. It may cause 

a fire or electric shock. 

Make sure to turn the power off before commencing any wiring 

work.  Otherwise  it  may  cause  electric  shock  or  damage  to 
equipment. 

Do not use any tester other than the one specified for testing. It 

may cause damage to equipment. 

 

Note 

Follow the requirements for the installation of the products in 

accordance with the Specifications. Otherwise it may cause 
malfunction. 

The products should not be installed in the following places, as it 

may cause damage to equipment: 

Place with plenty of air flow (close to a ventilation fan, air 

conditioner, or place with drafts) 

Place close to heating appliance 

Place with a constantly high temperature or humidity   

Place with lots of dust or insects 

Place with exhaust gas such as garage 

Place

 

where oil, dust, iron powder, chemicals, or hydrogen 

sulphide may occur or affect the products 

 

These instructions explain how to install and test UL Listed Nittan 
detectors and bases. 
 
For the details of each product, please refer to “Instruction Manual” 
on the website: http://www.nittan.com 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 

 

Table 1: UL Listed Product Instruction Manual

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 
 

CAUTION

!

 

Install the detectors/bases in accordance with these instructions, 
applicable  NFPA  standards,  local  codes,  and  the  authorities 
having jurisdiction. Failure to follow these instructions may result 
in  failure  of  detectors  to  initiate  an  alarm  condition.  Nittan  is  not 
responsible  for  detectors  and  bases  that  have  been  improperly 
installed, tested, or maintained. 

 

Table 2: Electrical box for base 

BASE Model 

Applicable electrical box 

3-1/2” Oct 

4” Oct 

4” Square 

EVA-UB4 

 

EVA-UB4-6 

 

 

 

EVA-S6 Base 

 

 

 

EVA-STB-RL 

 

EVA-STB-RL 

with 

STBA-ADP 

 

 

EVA-STB-SCI 

 

EVA-STB-SCI 

with 

STBA-ADP 

 

 

 

Connect wiring to the detectors/bases as shown in the Section2. 
Detectors and bases may be mixed on the same initiating loop as 
long  as  the  number  of  two-wire  powered  detectors  does  not 
exceed  the  specifications  of  the  control  panel.  For  the 
specifications of detectors/bases, see Table 3. 

 
 
 
 

Product category 

Model number 

Manual part 

number 

Version 

Control Panel 

NFU-7000 series 

LT-894NIT 

Rev 2.1 

Detector 

EVA-PY 

DW1401832 

Rev.K1 

EVA-PYH 

DW1401831 

Rev.K1   

EVA-H2 

DW1401833 

Rev.K1 

EVA-H2-H 
EVA-DPH 

DW1401834 

Rev.K1 

EVCA-P(-Z) 

DW1500110 

Rev.K2 

Base 

EVA-UB4 

DW1401959 

Rev.K1 

EVA-UB4-6 
EVA-STB-RL 

DW1401853 

Rev.K1 

EVA-STB-SCI 

DW1401852 

Rev.K1 

EVA-S6 Base 

DW1401960 

Rev.K1 

Module 

EVA-DIP-SCI 

DW1401989 

Rev.K1 

EVA-DOP-SCI 

DW1401991 

Rev.K1 

EVA-DOP 
-AC240V-SCI 

DW1401992 

Rev.K1 

EVA-SCI 

DW1401994 

Rev.K1 

EVA-SCM-SCI 

DW1401995 

Rev.K1 

EVA-MiniIP 

DW1401993 

Rev.K1 

EVA-ZMU-SCI 

DW1401990 

Rev.K1 

End of line 

PCE 

DW1401961 

Rev.K1 

Adapter Mounting 

Plate 

STBA-ADP 

DW1402124 

Rev.K1 

 

NITTAN COMPANY, LIMITED

 

1-54-5 SASAZUKA, SHIBUYA-KU, TOKYO 151-8535, JAPAN 

 

http://www.nittan.com

 

Summary of Contents for EVA-UB4

Page 1: ...te http www nittan com Table 1 UL Listed Product Instruction Manual CAUTION Install the detectors bases in accordance with these instructions applicable NFPA standards local codes and the authorities having jurisdiction Failure to follow these instructions may result in failure of detectors to initiate an alarm condition Nittan is not responsible for detectors and bases that have been improperly i...

Page 2: ... P 68mA max 47 5mA at 24VDC EVCA P Z 68mA max When connected to EVA ZMU SCI 20 5mA Voltage Ripple 20 maximum Sensitivity 1 78 Ft to 3 60 Ft Alarm Characteristics EVCA P 6VDC in series with 375R between Terminal 3 and Terminal 1 6 at 25 C EVCA P Z 6VDC between Terminal 3 and Terminal 1 6 at 25 C UL Ambient Installation Temperature 0 C to 49 C 32 F to 120 F Operating Temperature 10 C to 55 C 14 F to...

Page 3: ...t to optional equipment Output Normal status Close between N C COM Open between N O COM 3 6 5 1 3 6 5 1 UL Listed Module EVA ZMU SCI A A B B L L EVA UB4 EVA UB4 6 3 6 5 EVA UB4 EVA UB4 6 1 3 6 5 1 UL Listed Module EVA ZMU SCI A A EOL 10KΩ L L UL Listed Control Panel LOOP LOOP LOOP I 1 6 I 1 6 PCE 24V 24VG A L AUX PWR LOOP AUX PWR EVA S6 Base EVA S6 Base EVA MinilP L A A A I I NFU 7000 Series UL Li...

Page 4: ...emove and discard the dust cover 3 4 Use of detector guard Smoke detectors are not to be used with detector guards unless the combination has been evaluated and found suitable for that purpose Notes In the event of a false alarm clean and re install the detector If the detector still gives false alarms replace the detector 4 Testing Notes Before testing notify the proper authorities that the syste...

Page 5: ...icator fails to light check the power to the detector and the wiring in the detector base 10 Reset the heat detector at the control panel Detectors that fail these tests should be cleaned in accordance with MAINTENANCE Section in the instruction manual of the detector and retested If the detectors still fail these tests they should be returned for repair CAUTION Do not use heat guns used for paint...

Page 6: ...are 1 78 ft 3 60 ft 2 For EVA PY EVA PYH and EVA DPH Check that the detector gives an alarm condition within 40 seconds after the aerosol of which the concentration controlled with the Analyzer was introduced into the detector s head Check the red LED indicator is on and the green LED is flashing on the detector If the red LED indicator fails to light check the power to the detector and the wiring...