Nittan EVA-UB4 Installation Instructions Manual Download Page 5

DW1500274 

Rev.K3 

Mar  6,  2017 

Direct Heat Method 

  (Heat Calibur HO-HC11 Heat Detector Tester) 

1. 

Turn  Master  Power  switch  on  and  press  the  Power 
button. LCD Display and LED’s should light. 

2. 

Select  Test  Type  by  pressing  the  Test  Type  ↕  button, 

the LED will light to display selected test type: 

a. 

ROR - 

Rate of Rise Temperature Test 

b. 

FIXED -  Fixed Temperature Test 

3. 

Select Test Mode by pressing the Test Mode ↕ button, 

the LED will light to display selected test mode: 

c. 

STD - 

Standard Test Mode 

d. 

MULTI -  Multiple Test Mode 

4. 

Select  Temperature  Range  by  pressing  the  Temp 

Ran

ge  ↕  button,  the  LED  will  light  to  display  selected 

Temperature Range: 

a. 

HIGH -    High 

Temperature 

Range 

(190°F-210°F) - EVA-H2-H 

b. 

LOW -   

Low 

Temperature 

Range 

(100°F-135°F) - EVA-H2, EVA-PYH, EVA-DPH 

5. 

Press  and  hold  Start  Test  button  for  2  seconds  until 
“Ready” is displayed on LCD. 

6. 

Place the Heat Detector Tester over the detector to be 

tested to start the test, press the outer ring against the 

ceiling to start test. 

a. 

When the test has started a beep will sound, the 

test will continue as long as the outer ring makes 

contact with the ceiling. 

b. 

Hold  the  Heat  Detector  Tester  over  detector  until 

the detector alarms. 

7. 

Remove the Heat Detector Tester from the detector to 

stop  testing.  The  Heat  Detector  Tester  will  beep  twice 

when test is stopped, the fan will continue to run for 15 

seconds to cool unit. 

If the  unit  is not  removed  before  set  test  length  (60-90 

seconds),  the  unit  beeps  twice and  the  display  flashes 
between  “Error”,  and  “Timeout”  to  reflect  that  test 

stopped before the detector alarmed. 

8. 

If testing is complete, turn the Master Power switch off. 

9. 

The  red  LEDs  on  the  detector  should  light  with  the 

green  LED  flashing  when  the  temperature  at  the 

detector  reaches  the  alarm  set  point.  If  the  red  LED 

indicator  fails  to light,  check  the  power  to  the  detector 

and the wiring in the detector base. 

 

 

 

10.  Reset the heat detector at the control panel. Detectors 

that  fail  these  tests  should  be  cleaned  in  accordance 

with MAINTENANCE Section in the instruction manual 

of  the  detector  and  retested.  If  the  detectors  still  fail 

these tests they should be returned for repair. 

 

!

CAUTION

 

Do not use heat guns used for paint stripping or soldering 

pipes  as  these  heat  guns  generate  sufficient  heat  to 

damage heat detectors.   

 

For the smoke detector testing (Go / No-Go) 

1. 

For EVA-PY and EVA-PYH 

To test the optical detector, introduce a certain amount 

of  aerosol 

into the detector’s head, using HSI FIRE & 

SAFETY Aerosol canned smoke testers 

“25S” or “30S”. 

Please follow the manufacturer’s recommendations on 

their use.   

For EVA-DPH 

Use Smoke Detector Sensitivity Analyzer Model 501-B 

(Gemini  Scientific  Corp.)  to  test  the  function  of  the 

EVA-DPH. 

Please follow the manufacturer

’s recommendations on 

their use except aerosol concentration setting. 

Set the concentration of the analyzer to 1.0 %/ft. for this 

testing. 

For EVCA-P(-Z) 

To test the optical detector, introduce a certain amount 

of  aerosol 

into  the  detector’s  head,  using  Solo  330 

Aerosol Dispenser with Solo A3 Smoke Detector Tester 

(No  Climb  Products  Ltd.).  Please  follow  the 
manufacturer’s recommendations on their use. 

2. 

For EVA-PY and EVA-PYH 

Check that the detector gives an alarm condition within 

15 seconds. Check the red LED indicator is on and the 

green  LED  is  flashing  on  the  detector.  If  the  red  LED 

indicator  fails  to light,  check  the  power  to  the  detector 

and the wiring in the detector base. 

For EVA-DPH 

Check that the detector gives an alarm condition within 

40  seconds  after  the  aerosol  introduced  into  the 

detector

’s head. Check the red LED indicator is on and 

the green LED is flashing on the EVA-DPH

 

combination 

detector. If the red LED indicator fails to light, check the 

power  to  the  detector  and  the  wiring  in  the  detector 

base. 

 

 

Summary of Contents for EVA-UB4

Page 1: ...te http www nittan com Table 1 UL Listed Product Instruction Manual CAUTION Install the detectors bases in accordance with these instructions applicable NFPA standards local codes and the authorities having jurisdiction Failure to follow these instructions may result in failure of detectors to initiate an alarm condition Nittan is not responsible for detectors and bases that have been improperly i...

Page 2: ... P 68mA max 47 5mA at 24VDC EVCA P Z 68mA max When connected to EVA ZMU SCI 20 5mA Voltage Ripple 20 maximum Sensitivity 1 78 Ft to 3 60 Ft Alarm Characteristics EVCA P 6VDC in series with 375R between Terminal 3 and Terminal 1 6 at 25 C EVCA P Z 6VDC between Terminal 3 and Terminal 1 6 at 25 C UL Ambient Installation Temperature 0 C to 49 C 32 F to 120 F Operating Temperature 10 C to 55 C 14 F to...

Page 3: ...t to optional equipment Output Normal status Close between N C COM Open between N O COM 3 6 5 1 3 6 5 1 UL Listed Module EVA ZMU SCI A A B B L L EVA UB4 EVA UB4 6 3 6 5 EVA UB4 EVA UB4 6 1 3 6 5 1 UL Listed Module EVA ZMU SCI A A EOL 10KΩ L L UL Listed Control Panel LOOP LOOP LOOP I 1 6 I 1 6 PCE 24V 24VG A L AUX PWR LOOP AUX PWR EVA S6 Base EVA S6 Base EVA MinilP L A A A I I NFU 7000 Series UL Li...

Page 4: ...emove and discard the dust cover 3 4 Use of detector guard Smoke detectors are not to be used with detector guards unless the combination has been evaluated and found suitable for that purpose Notes In the event of a false alarm clean and re install the detector If the detector still gives false alarms replace the detector 4 Testing Notes Before testing notify the proper authorities that the syste...

Page 5: ...icator fails to light check the power to the detector and the wiring in the detector base 10 Reset the heat detector at the control panel Detectors that fail these tests should be cleaned in accordance with MAINTENANCE Section in the instruction manual of the detector and retested If the detectors still fail these tests they should be returned for repair CAUTION Do not use heat guns used for paint...

Page 6: ...are 1 78 ft 3 60 ft 2 For EVA PY EVA PYH and EVA DPH Check that the detector gives an alarm condition within 40 seconds after the aerosol of which the concentration controlled with the Analyzer was introduced into the detector s head Check the red LED indicator is on and the green LED is flashing on the detector If the red LED indicator fails to light check the power to the detector and the wiring...

Reviews: