b. Outdoor Compensated Supply Air Temperature Control
The set point of the supply air temperature can be guided to improve the adjustment to room heat losses from the outside
temperature. This ensures that the cooling of room walls is compensated during the cold season.
The setpoint of the supply air temperature is determined outside temperature-dependent by means of a control curve with 8
points.
Example:
Outdoor temperature [°C]
Supply Temperature [°C]
-20
25
-15
24
-10
23
-5
23
0
22
5
20
10
18
15
18
Control function
↑
Mode
->
Outdoor comp supply
↓
Outdoor comp setp
↑
-20.0
°C
= 25.0
°C
-15.0
°C
= 24.0
°C
-10.0
°C
= 23.0
°C
↓
Outdoor comp setp
↑
-5.0
°C
= 23.0
°C
0.0
°C
= 22.0
°C
5.0
°C
= 22.0
°C
↓
Outdoor comp setp
↑
10.0
°C
= 18.0
°C
15.0
°C
= 18.0
°C
↓
Summary of Contents for EVO-R
Page 1: ...EVO R COMPACT AIR HANDLING UNIT WITH ROTARY HEAT RECOVERY ...
Page 129: ...129 Fig 170 Fig 171 ...
Page 130: ...130 Fig 171 ...
Page 132: ...132 Fig 173 Fig 174 ...
Page 133: ...133 Fig 174 ...
Page 135: ...135 Fig 176 Fig 177 ...
Page 136: ...136 Fig 177 ...
Page 138: ...138 Fig 179 Fig 180 ...
Page 139: ...139 Fig 180 ...
Page 141: ...141 Fig 182 Fig 183 ...
Page 142: ...142 Fig 183 ...
Page 144: ...144 Fig 185 Fig 186 ...
Page 145: ...145 Fig 186 ...
Page 147: ...147 Fig 188 Fig 189 ...
Page 148: ...148 Fig 189 ...
Page 150: ...150 Fig 191 Fig 192 ...
Page 151: ...151 Fig 192 ...
Page 153: ...153 Fig 194 Fig 195 ...
Page 154: ...154 Fig 195 ...
Page 155: ...155 ...