34
The setpoint of the room temperature is determined outside temperature-dependent by means of a control curve with 8 points.
Example:
Outdoor temperature [°C]
Room Temperature [°C]
-20
18
-15
18
-10
20
-5
22
0
23
5
23
10
24
15
25
Control function
↑
Mode
->
Outd comp room
↓
Outdoor comp setp
↑
-5.0
°C
= 23.0
°C
0.0
°C
= 22.0
°C
.0
°C
= 20.0
°C
↓
Outdoor comp setp
↑
-20.0
°C
= 25.0
°C
-15.0
°C
= 24.0
°C
-10.0
°C
= 23.0
°C
↓
Outdoor comp setp
↑
10.0
°C
= 18.0
°C
15.0
°C
= 18.0
°C
↓
If cascade control
↑
Max/min supply setp
Max: XX.X
°C
Min: XX.X
°C
↓