Compressor

 COOLING CIRCUIT

Scroll hermetic compressors with 2-pole electric motors. All the compres

-

sors are equipped with guard resistance, inner electronic thermal protec

-

tion device with centralised manual reset.

System side heat exchanger

Braze welded AISI 316 steel plate heat exchanger. The heat exchanger is 

insulated externally with closed cell neoprene anti-condensation material. 

When the unit is not running, it is protected against formation of ice by an 

electric resistance.

Source side heat exchanger

 

Microchannels heat exchanger that guarantees higher thermal exchange 

yield. Circuit that optimises the liquid distribution in the coil, which is arran

-

ged with V beam geometry with open angle. The configurator has always 

the standard copper/aluminium coils available.

Recovery side heat exchanger (optional)

Braze welded AISI 316 steel plate heat exchanger. The heat exchanger is 

insulated externally with closed cell neoprene anti-condensation material. 

When the unit is not running, it is protected against formation of ice by an 

electric resistance.

Dehydrator filter

Hermetic-mechanical with cartridges made of ceramic and hygroscopic 

material, able to withhold impurities and any traces of humidity present in 

the cooling circuit.

Mechanical thermostatic valve

With external equaliser positioned at evaporator outlet, it modulates the 

flow of gas to the evaporator, according to the heat load, in order to ensure 

correct heating level of the intake gas.

Electronic thermostatic valve

Compared to the classic thermostatic valve, the electronic thermostatic val

-

ve stands out for its best overheating regulation. This way, the evaporator is 

fully exploited increasing the machine yield.

Its use in applications intended for comfort provides important benefits, 

especially in the presence of variable loads, as it allows you to maintain 

maximum efficiency with any outdoor air temperature.

In industrial applications, where temperature changes are often required in 

relation to various environmental conditions, the electronic valve is ideal to 

prevent the system from continuous calibration, thus adapting the system 

to different load conditions, making it independent.

Solenoid valves (3)

The valves close when the compressor switches off, blocking the flow of 

refrigerant gas to the evaporator, recovery and the coil.

Liquid indicator

It is used to verify that the expansion system is powered correctly and the 

presence of humidity in the cooling circuit.

STANDARD HYDRAULIC CIRCUIT

 Water filter

Equipped with steel filtering mesh, it prevents the heat-exchanger from 

clogging system side due to any impurity inside the circuit.

Differential pressure switch

Positioned before and between the input and output of the heat exchanger, 

its task is to ensure water circulation. If triggered, it locks the unit.

Throttle valve

Useful for cutting out the hydraulic system in case of maintenance, for 

example, to clean the filter.

In the event of variable flow rate, the motorised hydronic valves can 

intercept one or more modules to reduce the flow rate in low heat load 

conditions.

COMPONENTS OF THE STRUCTURE AND FANS

Structure

Supporting structure made of hot-dipped galvanised steel sheets, painted 

with polyester powders, built to guarantee easy accessibility for service and 

maintenance.

Standard fan unit

Equipped with accident-prevention net, it consists of axial fans and 6-pole 

motor with external rotor and protection rating IP54. Moreover, the motor 

is equipped with inner thermal protection with automatic reset. 

Inverter fans (option)

Continuous modulation of revolution speed according to the condensation 

pressure, highly efficient motor for low energy consumption.

CONTROL AND SAFETY COMPONENTS

Manually reset high pressure switch

With fixed calibration, placed on the high pressure side of the cooling cir

-

cuit, it inhibits the operation of the compressor if abnormal work pressure 

occurs

Low pressure transducer

Placed on low pressure side of cooling circuit, it signals the work pressure 

to the control board, generating a pre-warning in case abnormal pressure 

occurs.

High pressure transducer

Placed on the high pressure side of the cooling circuit, signals the work 

pressure to control board, generating a pre-warning in case abnormal 

pressure occurs

Control and electric power board

complete with:

-   - spring type control circuit terminal board,

-   Circuit breakers and contactors for compressors and fans,

-   terminals for REMOTE PANEL

-   - evaporator pump and recovery pump control consent relay (only for 

versions without pump units),

-   - all numbered cables.

-   DOOR-LOCK ISOLATING SWITCH

-   pump evaporator and pump recovery unit control consent relay (only for 

versions without pump units).

-   Act on the opening lever of the control

3  Only with mechanical thermostatic valve

Summary of Contents for NRV 0550

Page 1: ...EN Technical Manual TRANSLATION FROM ORIGINAL 5523421_02 22 02 OUTDOOR CHILLER MICROCHANNEL COILS EASY AND QUICK TO INSTALL COMPACT MODULE RELIABILITY AND MODULARITY NRV 0550...

Page 2: ......

Page 3: ...ce and in depth engineering research and it is manufactured using top quality materials and cutting edge technologies In addition the CE mark guarantees that our appliances fully comply with the requi...

Page 4: ...15 BASIC PRINCIPLES ON MICROCHANNEL COIL CORROSION 16 CLEANING MICRO CHANNEL COIL 16 OPERATING RANGE 17 PERFORMANCE SPECIFICATIONS 18 GENERAL SPECIFICATIONS 18 ELECTRICAL DATA 19 DIMENSIONS AND WEIGHT...

Page 5: ...e ci dessus est conforme aux normes d harmonisation relatives de l Union Der Gegenstand der genannten Erkl rung entspricht den diesbez glichen harmonisierten Normen der europ ischen Gemeinschaft El o...

Page 6: ...200 L WSH 1202 WSH 1402 WSH 1602 WSH 1802 WSH 2002 WSH 2202 WSH 2502 WSH 2802 NRG 0802 L NRG 0804 L Bevilacqua VR Commercial Director Luigi Zucchi This declaration of conformity has been released und...

Page 7: ...low heat load conditions EXTENDED OPERATING RANGE This range can work at full load with outdoor temperature up to 50 C This occurs in the high efficiency versions and also for example in versions wit...

Page 8: ...t recovery Without heat recovery D With desuperheater 11 Version A High efficiency E Silenced high efficiency 12 Coils Aluminium micro channel O Painted aluminium microchannel R Copper Copper S Copper...

Page 9: ...refrigerant gas to the evaporator recovery and the coil Liquid indicator It is used to verify that the expansion system is powered correctly and the presence of humidity in the cooling circuit STANDA...

Page 10: ...e always a prompt diagnosis of the unit operation Creation of operation time periods required for efficient programming A self adaptive logic is used to defrost This logic allows you to adjust the num...

Page 11: ...c circuit system side System side heat exchanger plate heat exchanger Heat exchanger electric resistance Water filter Flow Switch Differential pressure switch Safety valve Manual air vent valve Automa...

Page 12: ...12 PRINCIPLE FUNCTIONING DIAGRAMS NRV0550 with mechanical thermostatic valve Schema frigorifero NYB Evaporator Condenser Condenser Evaporator...

Page 13: ...high pressure switch finned heat exchanger scroll compressor drier filter insulated pipe regulation line Pressure connection high pressure side temperature probe high pressure transducer low pressure...

Page 14: ...fold KREC Accessory kit to remote the electric power supply input to the back RIF Power factor correction Connected in parallel to the motor allowing about 10 reduction of input current COMPATIBILITY...

Page 15: ...te corrosion Within the manufacturing plants corrosive gas may result from the proces sing of chemicals or by the typical industrial processes used in manufactu ring Potential sources of risk to be co...

Page 16: ...oisture in the air is one such electrolyte Humid air contaminated with corrosive gasses further accelera tes the corrosion rate as the air s current carrying otential increases Temperature Chemical re...

Page 17: ...mend you first contact our technical sales service Note If the unit is installed in particularly windy areas you must provide a windbreak to prevent unit malfunctions It should be installed if wind sp...

Page 18: ...at exchanger Type plates Number no 1 Resistance no W Connections with Grooved Joints Diameter A in out 6 E in out 6 Desuperheater Heat Exchanger Type plates Number no 1 Resistance no W Connection type...

Page 19: ...GHTS Size Notes ver 0550 Electrical data Standard unit Height A mm 2480 E mm 2480 Width A mm 2200 E mm 2200 Length A mm 1190 E mm 1190 Vacuum weight A kg 1105 E kg 1105 Size Notes ver 0550 Electrical...

Page 20: ...24 61 48 38 80 63 51 0550E TA d b 10 25 35 46 10 25 35 46 10 25 35 46 10 25 35 46 TW out 4 7 10 15 Glycol 10 0 00 0 00 0 00 Pc 118 5 104 0 93 1 84 7 131 6 115 5 103 5 93 5 144 0 126 3 113 5 165 6 145...

Page 21: ...nsitive to the phenomenon of extra oxygenation of the water an event that can be encouraged by the incorrect positioning of some components This phenomenon can trigger corrosion processes and subseque...

Page 22: ...0 955 0 947 0 939 0 932 0 924 Pe 1 0 996 0 994 0 992 0 99 0 988 0 986 0 984 0 982 0 98 Dp 1 1 082 1 102 1 143 1 201 1 271 1 351 1 435 1 52 1 602 CORRECTIVE FACTORS GLYCOL Qwc Water flow rate correctiv...

Page 23: ...e at the moment of installation 1200 Xg Yg 1 3 2 4 Top View WEIGHT WITHOUT PACKING Module 1 Model Version Module kit Weight kg Barycentre mm Distribution of weights on the supports NRV 0550 00 no Hydr...

Page 24: ...C S p A Via Roma 996 37040 Bevilacqua VR Italia Tel 39 0442 633111 Fax 39 0442 93577 marketing aermec com www aermec com Aermec reserves the right to make all modification deemed necessary for improvi...