20
COOLING MODE VERSIONS °
YIELDS AND ABSORPTION DIFFERENT THAN NOMINAL
Data 14511:2013
TA b.s.
Inlet water temperature with dry bulb (°C)
TW(out)
Temperature of the water produced °C
Glycol
Ethylene glycol percentage (%)
PC
Cooling capacity [kW]
Pe
Input power (kW)
Qn
Water flow rate [l/h]
∆P
Pressure drop to the exchanger (kPa)
-
Conditions outside the operating range
Capacities and pressure drops in the heat exchangers calculated with ∆T 5 °C
Note
For operating conditions different to those declared refer to the selection program available on www.aermec.com
0550A
TA d.b.
10
25
35
46
10
25
35
46
10
25
35
46
10
25
35
46
TW (out)
4
7
10
15
Glycol
10%
0.00%
0.00%
0.00%
Pc
123.2
109.1
98.0
84.7
135.9
120.3
108.1
93.3
147.7
130.8
117.6
-
168.7
149.6
134.7
-
Pe
22.3
28.3
33.8
41.3
23.2
29.3
34.9
42.6
24.2
30.4
36.0
-
26.2
32.3
38.1
-
EER
5.52
3.85
2.90
2.05
5.85
4.10
3.10
2.19
6.09
4.31
3.27
-
6.43
4.63
3.54
-
Qn
22441
19854
17830
15388
23461
20754
18638
16104
25550
22609
20315
-
29257
25921
23325
-
∆P
49
39
31
23
51
40
32
24
61
48
38
-
80
63
51
-
0550E
TA d.b.
10
25
35
46
10
25
35
46
10
25
35
46
10
25
35
46
TW (out)
4
7
10
15
Glycol
10%
0.00%
0.00%
0.00%
Pc
118.5
104.0
93.1
84.7
131.6
115.5
103.5
93.5
144.0
126.3
113.5
-
165.6
145.5
131.1
-
Pe
23.9
29.7
35.2
42.5
24.8
30.7
36.3
43.7
25.7
31.7
37.4
-
27.5
33.7
39.5
-
EER
4.95
3.50
2.64
1.99
5.31
3.76
2.85
2.14
5.61
3.98
3.04
-
6.03
4.31
3.32
-
Qn
21579
18925
16933
15391
22718
19919
17855
16139
24891
21827
19602
-
28723
25203
22701
-
∆P
46
35
28
23
48
37
30
24
58
44
36
-
77
59
48
-
PRESSURE DROPS
The water flow rate is calculated with the following formula:
Q = Pc x 860 / ΔT.
Q Water flow rate (l/h)
Pc Cooling capacity (kW)
ΔT Water heat drop (°C)
Pressure drops are calculated with the following formula:
Δp = K x (Q)2
Δp Pressure drops (kPa)
Coefficient for the various sizes and versions
Q Water flow rate (l/h)
Versions without hydronic kit ''00'' only plate heat exchanger
Mod.
Ver.
System side heat exchanger
Desuperheater
K
Q min
Q max
CAU
K
Q min
Q max
CAU
l/h
l/h
dm
3
l/h
l/h
dm
3
0550
A
9,31318E-08
9300
26000
0550
E
9,31318E-08
9300
26000
K
Coefficient for various sizes and versions
Q min
Minimum water flow rate to the exchanger
Q max
Maximum water flow rate to the exchanger