NRL
2800
3000
COMPRESSOR THERMOMAGNETIC SWITCHES 400V
CIRCUIT 1°
CIRCUIT 2°
CIRCUIT 1°
CIRCUIT 2°
MTC1
62A
62A
51A
51A
mtc1a
62A
62A
51A
51A
mtc1b
-
-
51A
51A
mtc2
51A
51A
51A
51A
mtc2a
51A
51A
51A
51A
mtc2b
51A
51A
51A
51A
HIGH PRESSURE SWITCH WITH MANUAL RESET
PA (bar)
40
40
High pressure transducer
TAP (bar)
39
39
LOW PRESSURE TRANSDUCER
TBP (bar)
2
2
CHILLER CIRCUIT SAFETY VALVE
AP (bar)
45
45
BP (bar) only in heat pump
30
30
FANS THERMOMAGNETIC SWITCHES [°]
The calibration is carried out on a thermomagnetic switch (single ventilation line)
Fans °/L
7A
7A
7A
7A
Fans H°/HL
9A
9A
9A
9A
FANS THERMOMAGNETIC SWITCHES [M]
The calibration is carried out on a thermomagnetic switch (single ventilation line)
Fans °/L
7A
7A
7A
7A
Fans H°/HL
9A
9A
9A
9A
NUMBER OF FANS
No. fans °/L
4
4
4
4
No. fans H/HL
4
4
4
4
NRL
3300
3600
COMPRESSOR THERMOMAGNETIC SWITCHES 400V
CIRCUIT 1°
CIRCUIT 2°
CIRCUIT 1°
CIRCUIT 2°
MTC1
51A
51A
62A
62A
mtc1a
51A
51A
62A
62A
mtc1b
51A
51A
62A
62A
mtc2
62A
62A
62A
62A
mtc2a
62A
62A
62A
62A
mtc2b
62A
62A
62A
62A
HIGH PRESSURE SWITCH WITH MANUAL RESET
PA (bar)
40
40
High pressure transducer
TAP (bar)
39
39
LOW PRESSURE TRANSDUCER
TBP (bar)
2
2
CHILLER CIRCUIT SAFETY VALVE
AP (bar)
45
45
BP (bar) only in heat pump
30
30
FAN THERMOMAGNETIC SWITCHES [°]
The calibration is carried out on a thermomagnetic switch (single ventilation line)
Fans °/L
11A
11A
11A
11A
Fans H°/HL
13A
13A
13A
13A
FANS THERMOMAGNETIC SWITCHES [M]
The calibration is carried out on a thermomagnetic switch (single ventilation line)
Fans °/L
13A
13A
13A
13A
Fans H°/HL
18A
18A
18A
18A
NUMBER OF FANS
No. fans °/L
13A
13A
13A
13A
No. fans H/HL
-
-
-
-
31
INRLPY. 02.10 4086916_01