15
INRLPY. 02.10 4086916_01
7. TECHNICAL
DATA
7.1.
TECHNICAL DATA VERSIONS [H-HL]
COOLING
2800
3000
3300
3600
Cooling output
kW
H
666
734
846
908
HL
604
664
746
794
Total input power
kW
H
280
318
332
358
HL
308
348
374
408
Water flow rate
l/h
H
114550
126250
145510
156180
HL
103890
114210
128310
136570
Total pressure drops
kPa
H
40.2
40.4
46.9
45.7
HL
33.4
33.6
37.0
35.5
HEATING
2800
3000
3300
3600
Heating capacity
kW
H
768
854
936
1006
HL
Total input power
kW
H
252
282
310
332
HL
Water flow rate on heating
l/h
H
132.100 146.890 160.990
173.030
HL
Total pressure drop on heating
kPa
H
53.7
55.4
58.8
57.8
HL
Energy indices
EER
W/W
H
2.38
2.31
2.54
2.54
HL
1.96
1.90
1.99
1.95
ESEER
W/W
H
3.57
3.50
3.53
3.60
HL
3.47
3.43
3.44
3.41
COP
W/W
H
3.05
3.03
3.02
3.03
HL
ELECTRICAL DATA
Fuel feed
A
H
400V - 3 - 50 Hz
HL
Input current on cooling
A
H
482
551
592
618
HL
521
594
641
673
Input current on heating
A
H
454
522
558
579
HL
Maximum current
A
H
588
646
730
796
HL
Peak current
A
H
797
855
998
1064
HL
COMPRESSORS (SCROLL)
Number/Circuit
no./
no.
H
10/4
12/4
12/4
12/4
HL
FANS (AXIAL)
Quantity
no.
H
8
8
12
12
HL
12
12
16
16
Air
fl
ow rate, cooling only
m³/h
H
174800
173600
248400
244800
HL
131000
138800
173800
171400
Heat pump air
fl
ow rate
m³/h
H
169800
168000
234600
229200
HL
Input power
kW
H
13.6
13.6
20.4
20.4
HL
13.6
13.6
20.4
20.4
Input current
A
H
28.8
28.8
43.2
43.2
HL
28.8
28.8
43.2
43.2
Useful heads[1]
Pa
H
55
54
47
45
HL
-
-
-
-
FANS (INVERTER J)
Quantity
no.
H
8
8
12
12
HL
-
-
-
-
Input power
kW
H
13.6
13,.6
20.4
20.4
HL
-
-
-
-
Input current
A
H
28.8
28.8
43.2
43.2
HL
-
-
-
-
Useful heads[1]
Pa
H
55
54
47
45
HL
-
-
-
-
*
The water connections are all of the Victaulic type
[1]
The useful heads refer to the nominal air flow rate