![AERMEC NRL Technical Manual Installation Maintenance Download Page 12](http://html1.mh-extra.com/html/aermec/nrl/nrl_technical-manual-installation-maintenance_2861924012.webp)
280
300
330
360
REF
Current rephaser. Parallel connection with the motor makes the reduction
of input current possible.
It can only be installed when the machine is being made and must
therefore be specified when the order is placed.
°
RIFNRL2800
RIFNRL3000
RIFNRL3300
RIFNRL3600
L
H
RIFNRL2800
RIFNRL3000
RIFNRL3300
RIFNRL3600
HI
DCPX
This accessory allows correct operation with outside temperatures below
10°C and down to -10°C.
It is made up of an electronic regulation card that varies the fan rpm on the
basis of the condensation pressure (read by the high pressure
transducer), to keep it sufficiently high for the proper functioning of the unit.
It also allows correct heating operation with outside temperatures greater
than 30°C and up to 42°C.
°
78
79
81
81
L
standard
H
78
80
82
82
HI
standard
DCPX M
DCPX only for configurations with enlarged fans (M).
°
78
80
82
82
L
standard
DUALCHILLER
Simplified control system to switch on and off, and command, two
chillers (using Aermec GR3 command) in a single system, as if they were
a single unit.
°
•
•
•
•
L
•
•
•
•
H
•
•
•
•
HI
•
•
•
•
MULTICHILLER
Control system to switch the individual chillers on and off, and command
them, in a system in which several units are installed in parallel, always
ensuring a constant delivery to the evaporators.
°
•
•
•
•
L
•
•
•
•
H
•
•
•
•
HI
•
•
•
•
TRX1
The water accumulators with holes and supplementary electric heaters
leave the factory with plastic protection caps. Before loading the system,
if the installation of an electric heater is not envisaged it is compulsory to
replace the plastic caps with the special TRX1.
°
•
•
•
•
L
•
•
•
•
H
•
•
•
•
HI
•
•
•
•
PRM 1
FACTORY-ASSEMBLED ACCESSORY. Pressure switch with manual reset
(using a tool), electrically connected in series to the high pressure switch
on the compressor delivery pipe.
°
•
-
-
-
L
•
-
-
-
H
•
-
-
-
HI
•
-
-
-
PRM 2
FACTORY-ASSEMBLED ACCESSORY. Pressure switch with manual reset
(using a tool), electrically connected in series to the high pressure switch
on the compressor delivery pipe.
°
-
•
•
•
L
-
•
•
•
H
-
•
•
•
HI
-
•
•
•
12
INRLPY. 02.10 4086916_01
* The water connections are all of the Victaulic type
[
1] The useful heads refer to the nominal air flow rate
Summary of Contents for NRL