SOME EXAMPLES:
VMF_E18 (default)
* Centralised control enabled
* Water p
FCXI 50 / 80
FCXI 20 / 30 / 40
* With shutoff valve
DIP-SWITCH SETTING
Turn off the power to the unit. This
operation should be carried out in the
installation phase, by suitably trained
and qualified personnel only.
The dip-switches are on the electronic
board.
**Warning
: if the thermostats are
inserted in systems with Centralised
Control or Supervisor (e.g. VMF-E5),
it is necessary to set: Dip1=ON and
Dip2=OFF. The setting takes priority
over the presence of the valve and the
position of the probe.
Position
Functions
Dip 1
(Default
OFF
)
Check water valve / * Thermostat in centralised network (See table):
OFF
No shut-off valve
ON
Shutoff valve present / * Thermostat in centralised network:
Dip 2
(Default
OFF
)
Position water temperature probe / * Thermostat in centralised network (See table):
OFF
Water temperature probe downstream from shutoff valve / *Thermostat in centralised network
ON
Water temperature probe upstream from shutoff valve
Dip 3
(Default
OFF
)
Ventilation control:
OFF
Thermostat-controlled ventilation
ON
Continuous ventilation
Dip 4
(Default
OFF
)
Ventilation enabling:
OFF
Enabling normal band
ON
Enabling reduced band
Dip 5
(Default
OFF
)
Machine with two or four pipes
OFF
2-pipe fan coils
ON
4-pipe fan coils
Dip 6
(Default
OFF
)
the presence of the accessory
OFF
Resistance to integration is not present
ON
Presence of resistance to integration
Dip 7
(Default
OFF
)
Dead band
OFF
Dead band 5° C
ON
Dead band 2° C
They can be used to obtain the following functions: