background image

39

English

AGLL10/20NFJ 07/11_4528571_00

INSTALLATION

WARNING: check that the power sup-

ply is disconnected before carrying out 
any procedures on the unit.

WARNING: before carrying out any 

work, put the proper individual pro-
tection devices on.

WARNING: the device must be installed 

in compliance with the national plant 
engineering rules.

WARNING: the electrical connections, 

the installation of the fan coils and 
relevant accessories should be per-
formed by a technician who has the 
necessary technical and professional 
expertise to install, modify, extend 
and maintain systems, and who is able 
to check the systems for the purposes 
of safety and correct operation (in 
this manual they will be indicated 
with the general term "persons with 
specific technical skills"). 

In the specific case of electrical wirings, 

the following must be checked:

- measurement of the electrical system 

insulation strength

- continuity test of the protection wires

WARNING: install a device, main 

switch, or electric plug so you can 
fully disconnect the device from the 
power supply.

The essential indications to install the 

device correctly are given here.

The completion of all the operations in 

accordance with the specific require-
ments is however left to the experience 
of the installation engineer.

See also the installation manual of the 

FCLI unit and the user's manual pro-
vided with the grille unit.

Generally the best position of the fins is 

that which allows the launch of the air 
adhering to the ceiling for the coined 
effect, during cold functioning. 

The opening positions are indicated 

on the side section of the deflectors 
(GLL10N) for correct machine heating 
(20° opening) and cooling (10° open-
ing) operation.

For units with GLL20N grilles the deflec-

tor should be fully opened in the heat-
ing operation and it should be rotated 
halfway in the cooling operation.

Depending on the user's needs, the fins 

can be adjusted to the intermediate 
positions, or completely closed. Thanks 
to the special shapes of the fins, the 
machine can also function with the 
deflectors completely closed. 

Do not install at a height above three 

metres.

The FCLI unit is prepared for connec-

tions with channelling for the fresh air 
and for the delivery of treated air to an 
adjacent room. 

• I

NSTALLING

 

NEAR

 

A

 

WALL

If the unit is to be installed near a wall, 

the corresponding delivery outlet can 
be closed using the gasket supplied.

ELECTRICAL WIRINGS

The unit must be connected directly 

to an electrical outlet or to an 
independent circuit.

The FCLI cassette-type fan coils must 

be powered with a current of  230V 
~50Hz with an earth connection; 

the line voltage must however 
remain within the tolerance of ±10% 
compared with the nominal value.

To protect the unit against short 

circuits, fit an omnipolar thermal 
trip max. 2A 250V (IG) to the power 
line with a minimum contact opening 
distance of 3 mm.

The electrical power cable must be of 

the H07 V-K or N07 V-K type with 
450/750V insulation if inside a tube 
or raceway. Use cables with double 
H5vv-F type insulation for visible 
cable installation.

For all the connections, follow the 

wiring diagrams supplied with 
the device and shown in this 
documentation.

The electric box is supplied with 

obligatory accessories (GLLI - 
GLLI_N).

Summary of Contents for GLL10N

Page 1: ... A T I O N B E D I E N U N G S U N D I N S T A L L A T I O N S A N L E I T U N G MANUAL DE USO E INSTALACIÓN CORNICE DI MANDATA E D ASPIRAZIONE DELIVERY AND INTAKE FRAME GRILLE DE SOUFFLAGE ET D ASPIRATION AUSBLAS UND ANSAUGGITTER INVERTER PLAFON DE ENVÍO Y DE ASPIRACIÓN AGLL10 20NFJ 1107_4528571_00 GLL10N GLL20N ...

Page 2: ...non mentionnée dans ce manuel contac ter aussitôt le service après vente de votre secteur Lors de l installation de l appareil il faut prévoir l espace nécessaire pour les opérations d entretien et ou de réparation La garantie de l appareil ne couvre pas les coûts dérivant de l utilisation de voitures avec échelle mécanique d échafauda ges ou d autres systèmes de levée employés pour effectuer des ...

Page 3: ...eries to which this declaration refers complies with the following standardised regulations soddisfando così i requisiti essenziali delle seguenti direttive Direttiva Bassa Tensione LVD 2006 95 CE Direttiva Compatibilità Elettromagnetica EMC 2004 108 CE thus meeting the essential requisites of the following directives Low Voltage Directive LVD 2006 95 EC Electromagnetic Compatibility Directive EMC...

Page 4: ...hlich mit Sorgfalt behan deln Frágil manejar con cuidado Freccia alto Arrow high flèche haut Pfeil hoch Flecha alto 25Kg Pericolo Pericolo Pericolo Tensione Organi in movimento Danger Danger Danger Power supply Movings parts Danger Danger Danger Tension Organes en mouvement Gefahr Gefahr Gefahr Spannung Rotierende Teile Peligro Peligro Peligro Tensión Elementos en movimiento SIMBOLI DI SICUREZZA S...

Page 5: ...accessory that must be connected to the electronic cards applied to fan coils Consult the manu als of the fan coils and cards if they have been provided as an accessory and apply all safety precautions indi cated for the electronic cards WARNING the fan coil is connected to the power supply and water circuit Operations performed by unqualified personnel can lead to personal injury to the operator ...

Page 6: ...ing Cooling The night time comfort function Sleep Supervisor controlled operating mode VMF E5 See the accessories manual for complete information on its features VMF E4 FCLI GLLI10N FCLI GLLI20N VMF E4 VMF E4 FCLI SLAVE FCLI SLAVE FCLI MASTER LUNGHEZZA MAX 30 m VMF E5 VMF E4 VMF E4 VMF E4 MASTER 1 MASTER 2 MASTER 3 FCLI GLLI10N FCLI GLLI20N FCLI GLLI10N FCLI GLLI20N FCLI GLLI10N FCLI GLLI20N FCLI ...

Page 7: ...FCLI GLLI_N RS485 TTL TTL TTL RS485 RS485 VMF E5B VMF E5N MASTER 2 FCLI GLLI_N MASTER 64 FCLI GLLI_N VMF E4 VMF E4D TTL MAX 30m VMF E4 VMF E4D RS485 MAX 1000m VMF E4 VMF E4D WARNING the VMF E5 panel allows the management of the individual masters the slave units connected to each master cannot be individually managed from the VMF E5 panel but they acquire the settings of the master to which they a...

Page 8: ...GLLI_N card as shown 1 2 3 4 TX RX GND TTL MODE 5V 1 2 3 4 5 6 1 2 3 4 5 6 Characteristics of the cable to be used for the connection EIB Bus cable 4 poles shield Mutual max capacity 100nF km 800Hz Resistance max 130 ohm km Key A 4 pole shielded cable not supplied for connection betweenVMF E4 and GLLI_N B Shield folded on the cable for earth connection C Clamp made of plastic conductive material s...

Page 9: ...F E4 EXTERNAL CONTACT CONNECTION ECONOMY CONTROL WINDOW CONTROL CONNECTION MODBUS RS485 SERIAL TTL NETWORK CONNECTION M26 CONTROL BOARD 1 2 3 4 5 6 1 2 3 4 5 6 TX RX CE TX RX GND TTL GND CF A B GND GND MODE 5V MODBUS RS485 CE EXTERNAL CONTACT TTL SERIAL TTL WITH VMF E4 ECONOMY CONTROL WINDOW CONTROL ...

Page 10: ...t 5 A M13 V1 minimum speed output Voltage 230 Vac current 5 A M14 Support input not connected M26 Service control board M22 Control board for connection to the receiver CN2 SW water probe NTC 10Kohm CN1 SA air probe NTC 10Kohm CN3 SC auxiliary water probe NTC 10Kohm M15 M16 SR electric resistor tempera ture probe NTC 4Kohm 200 C M17 Out 0 10V Inverter reference Voltage 10 Vdc current 10 mA M18 GND...

Page 11: ...robe reading display of the data read by the probes display of the alarm log start of the Autotest procedure The new display card must have a layout as shown in the following figures AUX key Blue Red LED Yellow Green LED To exit the test correction functions an ON OFF command via VMF E4 panel or a change mode command AUTO V1 V2 V3 AUX must be given to the cassette OFF AUX V3 V2 V1 AUTO AUTOTEST AU...

Page 12: ...view other probes The number of flashes by the green LED indicates which probe is displayed see table Green LED Probe displayed 2 SW probe 3 Aux SW probe 4 SA probe 5 Resistor probe SR ALARMS LOG The receiver cyclically indicates the last 5 alarms occurred on the machine in the alarms log view mode yellow LED cyclically flashes 5 times and then remains off for 5 seconds red LED lights at the same ...

Page 13: ...ce is the selection of the correc tion that is linked to the season of the thermostat SEASON TYPE OF PROBE CORRECTION Ambient probe temperature cold Ambient probe temperature hot Parameters cold and hot can be dif ferent from one another and can take integer values between 0 and 6 C To set the hot value for example the fan coil should be set to winter mode and in standby after pressing the AUX key...

Page 14: ...irements V2 In this position the average ventilation speed V2 is always active regardless of thermostat requirements V3 In this position the maximum ventilation speed V3 is always active regardless of thermostat requirements Aux In this position the minimum Aux ventilation speed is always active VENTILATION CONTROL If a shut off valve is present dip1 ON the position of the probe can be man aged bo...

Page 15: ... mode Hot mode if the ambient temperature detected is above the setpoint of an interval equal to the dead band 2 C or 5 C it switches to the cold mode The dead band is decided through dip7 or rather if it has a dead band of 5 C dip7 OFF while if the dead band is 2 C dip7 ON HOT COLD MODE CHANGE OVER COLD SEASON CHANGEOVER THRESHOLD HOT SEASON CHANGEOVER THRESHOLD DIP SWITCH MEANING 12 C 22 C 35 C ...

Page 16: ...at the resistance to the startup of the thermostat is in the OFF state will then be activated only if the water temperature is below the threshold of qualification which is 35 C with normal bandwidth 31 C with band reduced The activation of the electrical resistan ce however provides management of ventilation as a function proportional to the error but where is the minimum gua ranteed speed V2 Thi...

Page 17: ...e probe Position Functions Dip 1 Default OFF Check water valve Thermostat in centralised network See table OFF No shut off valve ON Shutoff valve present Thermostat in centralised network Dip 2 Default OFF Position water temperature probe Thermostat in centralised network See table OFF Water temperature probe downstream from shutoff valve Thermostat in centralised network ON Water temperature prob...

Page 18: ... the water but on the sheer demand for the thermostat opera tion AMBIENT PROBEABSENT 2 PIPES In this case the thermostat operates as follows OFF Aux Mode The valve is closed The fan is off AUTO V1 V2 V3 mode The valve is always open Operating season always hot The ventilation runs On Off cycles The duration of the ON cycle is pro portional to the setpoint set in the VMF E4 panel The total duration...

Page 19: ...ases according to settings different from those dictated by the master AMBIENT PROBE the ambient control probe is not needed on slave fan coils be cause these can use the control probe of the master However if you want to avoid having micro climates it can be installed on the slaves that will then adjust with the respective probe In particular cases where the ambient probe on the master is faulty ...

Page 20: ...m the last command received from it The master will also send the OFF com mand to all the slaves The user inter face also gives the visual alarm AL 1 TTL NETWORK CONSTRAINTS The constraint concerns the management of the adjustment dead band this should be set on the master fan coil being that it is ignored on the slaves because both the setpoint and the operating season of these depend on the mast...

Page 21: ...ing cold functioning The opening positions are indicated on the side section of the deflectors GLL10N for correct machine heating 20 opening and cooling 10 open ing operation For units with GLL20N grilles the deflec tor should be fully opened in the heat ing operation and it should be rotated halfway in the cooling operation Depending on the user s needs the fins can be adjusted to the intermediat...

Page 22: ... possible replacement Remove the delivery frame Extract the thermostat card Open the thermostat box Replace the faulty fuses The fuses are 5 x 20 T series delayed from 2 A to 10 A WARNING for correct replacement the 2 A fuse must be inserted in loca tion F3 while the 10 A fuse must be inserted in F2 as shown in the image below Before installing the electric box the configuration of the electronic ...

Page 23: ...el agua instalaciones de 4 tubos VHL Valvola Valve Vanne Ventil Válvula Componenti non forniti Components not supplied Composants non fournis Nicht lieferbare Teile Componentes no suministrados Componenti forniti optional Optional components Composants en option Optionsteile Componentes opcionales Collegamenti da eseguire in loco On site wiring Raccordements à effectuer in situ Vor Ort auszuführen...

Page 24: ...rät gelieferte Schaltschema beziehen El cableado de las máquinas es sometido a actualizaciones constantes Por favor para cada unidad hagan referencia a los esquemas suministrados con la misma FCL GLL10N GLL20N SA LED CE GND CF A B GND RS485 TX RX GND TTL BL1 5 7 MA1 5 1 M MP VHL 4 3 2 1 F 10A F 2A RL1 RL2 RL3 RL4 RL5 RL6 RL7 L N N AUX RE MA Y2 Y1 N1 V3 V2 V1 N TR1 M28 M14 M27 C1 M25 M22 CN2 CN1 CN...

Page 25: ...ät gelieferte Schaltschema beziehen El cableado de las máquinas es sometido a actualizaciones constantes Por favor para cada unidad hagan referencia a los esquemas suministrados con la misma FCL GLL10N GLL20N CE GND CF A B GND RS485 TX RX GND TTL BL1 5 7 MA1 5 1 M MP 4 3 2 1 F 10A F 2A RL1 RL2 RL3 RL4 RL5 RL6 RL7 L N N AUX RE MA Y2 Y1 N1 V3 V2 V1 N TR1 M28 M14 M27 C1 M25 M22 CN2 CN1 CN3 L17 M21 M1...

Page 26: ...rve le droit de modifier à tous moments les données considérées nécessaires à l amelioration du produit Technical data shown in this booklet are not binding Aermec S p A shall have the right to introduce at any time whatever modifications deemed necessary to the improvement of the product Im Sinne des technischen Fortsschrittes behält sich Aermec S p A vor in der Produktion Änderungen und Verbesse...

Reviews: