24 / 36
TF6775_A_NOT_DXR230_REFERENCE
Aereco S.A.
Replacement
1. Ensure that the new (clean) filters are positioned in the right order.
-
G4 filters: the inscription “dust air side” on the filter must face the incoming air.
-
F7 filter: the arrow on the filter must follow the supply air path.
2. Ensure that the new (clean) filters are firmly pushed back into their slots.
3. Replace the access hatches with 2 screws.
4. Switch on the unit
5. Reset the filters in the MAINTENANCE : menu MAINTENANCE / filters status / filter reset
Fresh air
(outdoor)
G4 filter
Exhaust air
(indoor)
F7 filter
F7
G4