7 / 36
TF6775_A_NOT_DXR230_REFERENCE
Aereco S.A.
3.
INSTALLATION
3.1. LOCATION OF THE INSTALLATION
The unit must be installed into the heated space, in parts of the dwelling relatively
insensitive to noise, not in the unheated space (attic, etc.). Upper and lower
temperature limits for the main unit are 5°C and 50°C
Ductwork should be installed in the heated space. If not, they must be insulated
with 50 mm minimum of glass wool (or equivalent). The non compliance with these
conditions leads to the degradation of the heat recovery performance.
DXR Unit
Max. altitude of the product installation
2000 m
Temperature range of the installation place
5°C – 50°C
Humidity range of the installation place
5 % - 95 %
3.2. DXR UNIT
The caps on the DXR Unit must stay during the entire duration of the work, in order to
keep dust and pollution from getting into the boxes.
3.2.1. LOCATION
Before the installation, be sure of the solidity of the ceiling where you plan to install DXR
Unit.
·Weight of DXR Unit = 46 kg
The DXR Unit must be attached so that the gap between the ceiling and the top of the unit
is at least 10 mm, and positioned exactly horizontally (max 1° tolerance).
The non compliance to this requirement may lead to serious problems of condensate
evacuation.
Positionning of the DXR Unit
D > 10 mm
ceiling
ceiling