6.10 Pump Adjustment
No settings are required for the pump, which is set to 360 PSI by the manufacturer. This
pressure must be checked and adjusted (if required) after the burner has been ignited.
The only operation required in this phase is the application of a pressure gauge on the
appropriate pump attachment.
6.11 Air Damper Adjustment
The first time the burner is fired, leave the factory-set low and high fire settings unchanged.
6.12 Ignition Pilot Adjustment
Position the pilot and electrode using the dimension shown in Figure 6-16. The pilot works
correctly at pressures ranging from 3-4” W.C.
Figure 6-16: Ignition Pilot Adjustment
A =
1- 21/64”
Electrode
Pilot Flange