4.2 PILOT BURNER
The Pilot Burner (P/N
29700
) is located on the right-front of the Burner Plate. It contains an
ignition cable and a Pilot gas line connected to the bushing. Figure 4-1 shows the location of the
Pilot Burner and related components.
.
Figure 4-1: Pilot Burner, Main & Pilot Flame Detector Mounting Locations
The Pilot Burner may be hot, therefore care should be exercised to avoid burns. It is easier to
remove the Pilot Burner from the unit after it has cooled to room temperature. To
inspect/replace the Pilot Burner, perform the following procedure:
SIGHT GLASS
MAIN FLAME
DETECTOR
TO PILOT
GAS LINE
BLOWER
BLOWER FLANGE
BURNER PLATE
PILOT
BURNER
PILOT FLAME
DETECTORS