BMK 5000-6000 Boiler OPERATION-SERVICE-MAINTENANCE GUIDE
SECTION 4 – MAINTENANCE
OMM-0124_0A
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
Page
43
of
136
GF-208
Ph.: 800-526-0288
05/02/2017
PILOT REGULATOR PRESSURE TEST PROCEDURE Instructions
Figure 4-3a: BMK 5000/6000 Single Fuel Pilot Regulator Mounting Location
Figure 4-3b: BMK 5000/6000 Dual Fuel Pilot Regulator Mounting Location
PROPANE
PILOT
SOLENOID
VALVES
NATURAL GAS
TEE with 1/4"
PLUG
(Install manometer
here for Pilot
Regulator test)
PROPANE
TEE with 1/4" PLUG
(Install manometer
here for Pilot
Regulator test)
NATURAL GAS
PILOT SOLENOID
VALVES
PROPANE
PILOT
REGULATOR
NATURAL GAS
PILOT
REGULATOR
PILOT
REGULATOR
PILOT
SOLENOID
VALVES
TO AIR/FUEL
VALVE
GAS INLET
MANUAL
SHUT-OFF
VALVE
HIGH GAS PRESSURE SWITCH
- BMK 6000
–
10.5” W.C., 2.6 kPa
- BMK 5000
–
11.0” W.C., 2.7 kPa
UPSTREAM LOW
GAS PRESSURE SWITCH
- BMK 6000
–
8.5” W.C., 2.1 kPa
- BMK 5000
–
8.0” W.C., 2.0 kPa