BMK 5000/6000 BURNER INSPECTION Instructions
24. To reassemble, begin with the Burner assembly and reinstall all the components in the
reverse order that they were removed. The Burner may have a nut installed at the base
position to keep the Burner level while installing the Blower (Figure 4-5).
25. Ensure that the Pilot Burner and Pilot Flame Detectors cutouts in the Blower Flange are
properly aligned with the Burner Front Plate.
NOTE:
Figure 4-4a shows the duel fuel version with the extra lower propane gas train
.
Figure 4-4a: Burner Assembly Mounting Details – Right-Front View
(Continued)
AIR
FILTERS
GAS TRAIN
AIR/FUEL VALVE
WYE DUCT
BLOWER FLANGE
TURN-BUCKLE
MAIN FLAME
DETECTOR
3/8-16 HEX NUTS &
WASHERS (8)
PILOT BURNER
BLOWER
PILOT FLAME DETECTORS
BURNER FRONT PLATE
TURNBUCKLE