Benchmark 2500 - 3000 Boilers
CHAPTER 6 – SAFETY DEVICE TESTING
Page
84
of
204
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
OMM-0094_0E
03/20/2014
Ph.: 800-526-0288
GF-137
6.11 IGNITION SWITCH OPEN DURING IGNITION
The Ignition Switch (and the Purge Switch) is located on the Air/Fuel Valve. To check the
switch, proceed as follows:
Ignition Switch Open During Ignition
1. Set the unit’s
ON/OFF
switch to the
OFF
position.
2. Place the unit in Manual Mode and set the valve position between 25% and 30%.
3. Remove the Air/Fuel Valve cover (Figure 6-7) by rotating the cover counterclockwise to
unlock and lift up to remove.
4. Remove one of the two wires (#169 or #170) from the Ignition Switch (Figure 6-8).
5. Initiate a unit start sequence.
6. The unit should begin its start sequence and then shut down and display
IGN SWITCH
OPEN DURING IGNITION.
7. Replace the wire on the Ignition Switch and press the
CLEAR
button. The unit should
restart.
Figure 6-7: Air/Fuel Valve Cover Location
AIR/FUEL VALVE COVER
(Rotate Counter-Clock-Wise
to Remove
)
AIR/FUEL
VALVE
BLOCKED
INLET
SWITCH
BLOWER
PROOF
SWITCH