Benchmark 2500 - 3000 Boilers
CHAPTER 9 – RS232 COMMUNICATION
Page
118
of
204
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
OMM-0094_0E
03/20/2014
Ph.: 800-526-0288
GF-137
NOTE
The Sensor (S) Log can store up to 1200 records. Therefore, to
view the most recently logged record, enter “S” followed by 0
(zero) and then press Enter (i.e. S0 <Enter>). To view earlier
records in reverse chronological order, enter S and press Enter.
To go back 200 or 700 records, enter S200 or S700, etc. and
press Enter.
9.4.3 Sensor Log
The sensor values can be logged at a different rate if needed by setting the Sensor Log Interval
in the Diagnostics Menu. The log interval can vary from once every minute to once every day.
Table 9-3 shows a sample Sensor Log every 5 minutes for a boiler running in Constant Setpoint
mode.
Table 9-3: Sample Sensor Log Display
Setpt Outlet Outdr FFWD Aux
Inlet Exhst CO O2 Flow Date
Time
130
181
OPEN OPEN OPEN OPEN OPEN
0
.0
0
1/15/02 5:51pm
130
180
OPEN OPEN OPEN OPEN OPEN
0
.0
0
1/15/02 5:46pm
130
180
OPEN OPEN OPEN OPEN OPEN
0
.0
0
1/15/02 5:41pm
130
179
OPEN OPEN OPEN OPEN OPEN
0
.0
0
1/15/02 5:36pm
130
180
OPEN OPEN OPEN OPEN OPEN
0
.0
0
1/15/02 5:31pm
130
180
OPEN OPEN OPEN OPEN OPEN
0
.0
0
1/15/02 5:26pm
130
180
OPEN OPEN OPEN OPEN OPEN
0
.0
0
1/15/02 5:21pm
130
180
OPEN OPEN OPEN OPEN OPEN
0
.0
0
1/15/02 5:16pm
130
179
OPEN OPEN OPEN OPEN OPEN
0
.0
0
1/15/02 5:11pm
130
180
OPEN OPEN OPEN OPEN OPEN
0
.0
0
1/15/02 5:06pm