APPENDIX E
Benchmark 2.0LN Low NOx Boiler
GF-120
BOILER DEFAULTS
Installation, Operation and Maintenance Manual
OMM-0041_0E
Page 126 of 166 AERCO International Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
•
Ph: 800-526-0288
PR1:10/18/12
APPENDIX E: BOILER DEFAULT SETTINGS
Table E-1: Boiler Default Settings
MENU & OPTION
FACTORY DEFAULT
Setup Menu
Password
0
Language
English
Unit of Temp
Fahrenheit (ºF)
Comm Address
0
Baud Rate
9600
Configuration Menu
Internal Setpt
130°F
Unit Type
BMK Boiler LN
Unit Size
1500 MBH
Fuel Type
Natural Gas
Boiler Mode
Constant Setpoint
Remote Signal
(If Mode = Remote Setpoint, Direct Drive or Combination)
4 – 20 mA / 1-5V
Bldg Ref Temp
(If Boiler Mode = Outdoor Reset)
70°F
Reset Ratio
(If Boiler Mode = Outdoor Reset)
1.2
Outdoor Sensor
Disabled
System Start Tmp
(If Outdoor Sensor = Enabled)
60°F
Setpt Lo Limit
60°F
Setpt Hi Limit
195°F
Temp Hi Limit
195°F
Max Valve Position
100%
Pump Delay Timer
0 min